Security Enhancements & Emergency Generator Immokalee Airport (IMM)

Not priced — requires review of price-critical inputs.

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmAVCON, INC.Meets
Project LocationImmokalee, FloridaMeets
Fuel TypeDieselMeets
Size (kW) + QuantityLine 1: 1 × ? kVA · diesel · 240V, 1 PH · permanentMeets
Send to distributorEvidence packet attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Evidence Packet - Security Enhancements & Emergency Generator Immokalee Airport (IMM) - Due Jul 31, 2026
AttachmentSecurity Enhancements & Emergency Generator Immokalee Airport (IMM).pdf
[DISTRIBUTOR NAME], We have a bid opportunity in East Naples, FL that fits your coverage area. Details below. Opportunity: Security Enhancements & Emergency Generator Immokalee Airport (IMM) Contracting Agency: County of Collier, FL Location: East Naples, FL Due Date: Jul 31, 2026 Key Specs: 1 × generator The evidence packet is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Review needed
Bid value
$0.00
Checks reviewed
0/51 reviewed
Pricing inputs0.48

No defensible Blue Star price is available yet. Not priced — requires review of price-critical inputs.

Found value

$0.00

Configurator/list/base price
$0.00
Active manual adders
$0.00
Reviewed list/base price
$0.00
Distributor net
$0.00
1 × permanent
diesel · Not charged
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AIAVCON, INC.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1AVCON, INC. 5555 E. Michigan Street, Suite 200 Orlando, FL 32822

25-8391 - Authorization to Advertise_FE - page 1Daniel J. Nickols, Jr., P.E.

Project Location

AIImmokalee, Florida

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1Immokalee, Florida

Project Application

AIAirport emergency/standby power

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 153Generator shall be used for standby emergency service to provide continuous electrical service during interruption of normal power.

Generator Requirements35
Rating Type / Application

AIStandby emergency, NFPA 110 Level 1, Tier 2

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151NFPA 110 for Level 1 loads

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151Generators to be rated as Tier 2

Fuel TypePricing input

AIDiesel

25-8391 Bid Schedule - page 1DIESEL-POWERED EMERGENCY BACKUP GENERATOR, INSTALLED, TESTED, AND COMPLETE

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 153No.2 diesel fuel

Size (kW) + QuantityPricing input

AILine 1: 1 × ? kVA · diesel · 240V, 1 PH · permanent

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1531. As noted on drawings.

25-8391 Bid Schedule - page 1DIESEL-POWERED EMERGENCY BACKUP GENERATOR, INSTALLED, TESTED, AND COMPLETE

Voltage + PhasePricing input

AIphase: 1 · voltage: 240V

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 153240 volts, 1 phase, 3 Wire.

Alternator Rating / Temp Rise

AI

No source-backed value found

Voltage Regulator

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 154The complete unit shall be equipped with a PMG (permanent magnet generator) to allow UPS systems and elevator systems to be connected to emergency system with no effect on emergency system performance.

Generator Space Heater

AI

No source-backed value found

Control Panel

AIGenerator mounted NEMA 1 type vibration isolated 14 gauge steel control panel, NFPA 110 Level 1

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 158A generator mounted NEMA 1 type vibration isolated 14 gauge steel control panel shall be provided to meet requirements of NFPA 110 for Level 1 systems.

Control Panel Options / Accessories

AIDigital voltmeter (+/-0.5%), digital ammeter (+/-0.5%), ammeter-voltmeter phase selector switch, remote automatic starting controls, voltage level adjustment rheostat (+/-5%), digital frequency meter (+/-0.5%), dry contacts for remote alarms, three position function switch (run/off/auto), NFPA 110 shutdown equipment (overcrank, high engine temperature, low lube oil pressure, overspeed, remote emergency stop), NFPA 110 alarms (overcrank, low water temperature, high engine temperature prealarm, high engine temperature, low lube oil pressure prealarm, low lube oil pressure, overspeed, low fuel main tank, EPS supplying load, control switch not in AUTO, battery charger malfunctioning, low voltage in battery, lamp test, common alarm, low starting air pressure, low starting hydraulic pressure, air shutdown damper), manual emergency shutdown mounted to exterior of building

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 158Voltmeter, +/- .5% accuracy (digital type)

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 158Three position function switch marked "run""off""auto"

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 159Manual Emergency shutdown. Mounted to exterior of building

Remote Annunciator

AIRemote mounted annunciator panel with audible and visual warning, powered by generator battery, individual visual signals for generator operating and battery charger malfunction, individual visual signals plus common audible signal for low oil pressure, low water temperature, excessive water temperature, low fuel, overcrank, overspeed; connected to BMS system

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 160A panel shall be provided for remote mounting as shown to give audible and visual warning of fault or alarm conditions in the generator set, battery charger and levelmeter.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 160Connect annunciator circuits to BMS system.

Enclosure Type + Material

AILevel 2 (75dB max) UL2200 listed aluminum enclosure, wind rated 160MPH per ASCE 7-05 exposure D category 1

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156The enclosure shall be wind rated to 160MPH per ASCE 7-05 exposure D, category 1 importance factor.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156The generator shall be enclosed in a level 2 (75db max) UL2200 listed aluminum enclosure.

Sound Attenuation

AILevel 2 (75 dBA max at 7m/23 ft.)

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 153Sound Level - Mechanical sound level where all generator sets are fully loaded shall be not greater than 75 dBA at 7 m (23 ft.).

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156level 2 (75db max)

Enclosure / Auxiliary-Power Accessories

AILockable doors, integral louvers, rodent barriers, lifting base, fully enclosed exhaust silencer, stair/handrail assembly for maintenance access, load center in enclosure

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156Rodent barriers shall be integrated into the enclosure.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156Lockable doors shall provide for easy access to all major generator and engine components.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156The exhaust silencer shall be fully enclosed.

Circuit Breaker(s)

AIMain line circuit breaker with electronic trip unit, LSI adjustability and ground fault alarm

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 152Main line circuit breakers shall have an electronic trip unit with LSI adjustability and ground fault alarm.

Generator Circuit Breaker

AIMain line circuit breaker with electronic trip unit, LSI adjustability and ground fault alarm

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 152Main line circuit breakers shall have an electronic trip unit with LSI adjustability and ground fault alarm.

Engine Filters

AIAir filters, fuel filters, fuel pressure gauge, lubricating oil cooler with filters, oil pressure gauge, full flow filtration with bypass valve, primary fuel filter, fuel/water separator

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 155full flow filtration with bypass valve

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 155A fuel/water separator shall protect the fuel system from water damage.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 155primary fuel filter between the fuel tank and transfer system to screen large contaminants

EPSS Class / Level

AINFPA 110 Level 1

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151NFPA 110 for Level 1 loads

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151level 1 generator

Exhaust Connector End Fittings

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 152Flexible exhaust piping

Generator Control Alarms

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 158Equipment for shutdown required by NFPA 110: a. Overcrank b. High engine temperature c. Low lube oil pressure d. Overspeed e. Remote emergency stop

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 15911. Equipment for Controls required by NFPA 110 a. Manual Emergency shutdown. Mounted to exterior of building

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1581) overcrank 2) low water temperature less then $ 7 0^{\circ} \mathrm{F} $ $ (2 1^{\circ} \mathrm{C}) $ 3) high engine temperature prealarm 4) high engine temperature 5) low lube oil pressure prealarm 6) low lube oil pressure

Generator Breaker Settings / Trip

AIElectronic trip unit with LSI adjustability and ground fault alarm

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 152Main line circuit breakers shall have an electronic trip unit with LSI adjustability and ground fault alarm.

Vibration Isolators

AIRubber pad type isolators on concrete base

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 157The engine-generator shall be mounted on rubber pad type isolators. A concrete base shall be provided as specified by the manufacturer.

Voltage / Frequency Transient Testing

AIMaximum instantaneous voltage dip not greater than 15% on motor starting inrush (light beam oscillograph); transient response per ISO 8528

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 154Block Load Acceptance - Transient response shall conform to ISO 8528 requirements.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 153Motor Starting - Motor starting inrush shall result in maximum instantaneous voltage dip not greater than 15% as measured by light beam oscilligraph.

Battery Compartment Heater

AIBattery heaters provided as part of generator auxiliary systems via mini-power zone

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151battery chargers, battery heaters, and block heaters, where indicated on plan drawings

Drawing Generator Rating / One-Line

AITerminal Bldg one-line (T504): ATS replaces existing manual transfer switch; 400A 3-pole main breaker; connected load 16.05 KVA, demand 2.00 KVA. Generator kW rating not explicitly shown on one-line. Generator referenced in enlarged plan: 'PROVIDE NEW GENERATOR WITH EXTERIOR HOUSING DIESEL BELLY TANKS, AND CONCRETE PAD.'

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 20REMOVE EXISTING MANUAL TRANSFER SWITCH. REPLACE WITH ATS.

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 9PROVIDE NEW GENERATOR WITH EXTERIOR HOUSING DIESEL BELLY TANKS, AND CONCRETE PAD. REFER TO ONE-LINE DIAGRAM AND DIV. 26.

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AITerminal Bldg one-line (T504): Main circuit breaker 400A 3-pole; Surge suppression device 30A 3-pole; branch breakers 20A 1-pole and 50A 1-pole. Generator main line circuit breaker rating not shown on one-line.

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 20MAIN CIRCUIT BREAKER

Jacket Water Heater

AIUnit mounted thermal circulation type water heaters with thermostatic switch, 50% ethylene glycol antifreeze, maintaining jacket water at 90°F in 30°F ambient; Kim-Hotstart, Chromalox or accepted substitution

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 155The engines shall be provided with antifreeze (a solution of 50% ethylene glycol) and suitable unit mounted thermal circulation type water heaters incorporating a thermostatic switch to maintain engine jacket water to $ 9 0^{\circ} \mathrm{

Exhaust Silencer

AICritical exhaust silencer, fully enclosed, extreme noise attenuation per engine manufacturer recommendations

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 157A critical exhaust silencer shall be provided in accordance to the engine manufacturer's recommendations for silencing. The silencer shall provide extreme noise attenuation for environments with low background noise and slight noise emissio

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156The exhaust silencer shall be fully enclosed.

Battery and Battery Charger

AICurrent limiting battery charger, float 1.4V/cell, equalize 1.6V/cell, overload protection, silicon diode full wave rectifiers, voltage surge suppressor, DC ammeter, DC voltmeter, fused AC input, 120VAC single phase input, minimum 6A output, auxiliary contact on charger failure; Lamarche A46 or equal

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 156Current limiting battery charger shall be furnished to automatically recharge batteries. Charger shall float at 1.4 volts per cell and equalize at 1.6 volts per cell. It shall include overload protection, silicon diode full wave rectifiers,

Fuel Tank + Accessories

AIDouble wall above-ground base mounted sub-base tank, minimum 72 hour capacity at 75% rated load, UL listed; low level alarm at 48 hours full load consumption, minimum tank size 133% of low level alarm; internal leak detection monitor in inner cavity; automatic tank gauge

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 157Fuel storage tank shall include an internal leak detection monitor device in the inner cavity.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 157The tank shall be a double wall above-ground base mounted with a minimum 72 hour capacity at 75% rated load.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 152Automatic tank gauge

Factory Testing

AI

No source-backed value found

Field Quality Control / Site Acceptance

AISite test: installation check and building load test by manufacturer's local representative, including NFPA 110 Level 1 tests, simulated power outage test for automatic start-up, transfer, and shutdown. Load bank test: resistive dry load banks, 1 hour 50%, 1 hour 75%, 3 hours 100%, 10 minutes cool down, with 15-minute interval logging of ambient temperature, amperes, hertz, oil pressure, water temperature, battery charging, noise level dBA, exhaust stack temperature

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 161An installation check and building load test shall be performed by the manufacturer's local representative.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 162After the building load test, a load bank test will be performed. This test shall be done with resistive dry load banks

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 161The tests shall include all tests specified by NFPA 11 Level 1.

Load Bank

AIResistive dry load bank test: 1 hour 50%, 1 hour 75%, 3 hours 100%, 10 minutes cool down; 15-minute interval logging; fuel for load test included in bid

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1621. 1 hour 50% 2. 1 hour 75% 3. 3 hours 100% 4. 10 minutes cool down

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 162Fuel for load test to be included in bid

Switchgear / Paralleling

AI

No source-backed value found

Warranty

AIMinimum 2 years from date of initial acceptance, manufacturer's and dealer's standard warranties

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 151Warranty - Equipment furnished under this section shall be guaranteed against defective parts or workmanship under terms of the manufacturer's and dealer's standard warranties, but in no event shall it be for a period of less than two (2) y

Generator Overload Capacity

AI

No source-backed value found

ATS Requirements13
ATS Quantity

AIquantity: 1 · required: Yes · instances: tag: — · rating: —

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 20REMOVE EXISTING MANUAL TRANSFER SWITCH. REPLACE WITH ATS.

25-8391 Bid Schedule - page 1AUTOMATIC TRANSFER SWITCH, INSTALLED, TESTED, AND COMPLETE

ATS Manufacturer / Model

AIAsco Series 300

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 171Asco Series 300.

ATS Ratings

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 168Normal and emergency full load current and voltage ratings at 60 cycles shall be as shown on plans.

Transition Type

AIOpen transition (double throw, mechanically interlocked, break-before-make) with optional delayed transition accessory

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 172The transfer switch shall be double throw, actuated by two electrical operators, momentarily energized and connected to the transfer mechanism by a simple overcenter linkage

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 173A neutral position shall not be possible under normal electrical operation unless a delayed transition accessory is required for switching highly inductive loads.

Poles / Neutral Configuration

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 168Transfer switches shall be a Three (3) pole type.

ATS Enclosure Type

AIICS 6, Type 1; NEMA 4X stainless steel

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 177Enclosure: ICS 6, Type 1.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 177NEMA 4X stainless steel.

ATS Features / Accessories

AIDouble throw with two electrical operators; time delay relays 0-300 seconds; manual operator (full rated load); multi-tap voltage selection plug; service entrance label; external key-operated selector switch; ASCO microprocessor controller with LCD display; voltage/frequency monitoring each phase both sources; undervoltage/overvoltage/underfrequency/overfrequency settings; password protection; non-volatile memory; program/run switch; pre-transfer signal 0-120 seconds; plant exerciser (7 day, 0-600 min load/no load); retransfer mode manual or automatic; test pushbutton (disabled/load/no load); pilot lights; test switch; molded case switch Square D type LHL

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 174The automatic transfer switches shall be controlled by an ASCO microprocessor-based controller

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 172double throw, actuated by two electrical operators

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 176Protective switching devices shall be fixed mount molded case switch, Square D type LHL or accepted equivalent.

ATS Transfer Timing

AI

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 175A time delay shall be provided for engine failure to start, adjustable from 0 to 6 seconds.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 175A time delay shall be provided to override a momentary power outage or voltage fluctuation, adjustable from 0 to 120 seconds.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 175A time delay shall be provided for the neutral position, adjustable from 0 to 120 seconds.

ATS Auxiliary Contacts

AI2 auxiliary contacts on main shaft (1 closed on normal, 1 closed on emergency); 2 sets relay contacts (open/close on loss of normal power); bell alarm and auxiliary switch wired to terminals; 2 SPST contacts for generator start (5A 250VAC); 4 SPST contacts for control (10A 250VAC); 3 SPDT contacts for control (10A 250VAC)

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 174bell alarm and auxiliary switch wired out to terminals for Owner's use.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 172two auxiliary contacts on the main shaft; one closed on normal, the other closed on emergency. In addition, two sets of relay contacts shall be provided to open and close upon loss of the normal power supply.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 176Two (2) SPST contacts for generator start, rated 5A, 250V AC

ATS In-Phase Monitor

AI

No source-backed value found

ATS Engine Exerciser

AIPlant exerciser adjustable in 15 minute increments; selectable disabled or 7 day interval, 0-600 minutes load or no load; test pushbutton mode (disabled, load, or no load)

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 176Plant exerciser, selectable - disabled or 7 day interval, 0-600 minutes load or no load

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 173The transfer switch shall automatically exercise the generating plant a no load or loaded condition. Exerciser shall be adjustable in 15 minute increments.

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AI1 ATS at Terminal Building (T504 one-line diagram): 3-pole with switched neutral, service entrance rated, replacing existing manual transfer switch. Rating not explicitly stated. Mounted to existing cabinet.

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 20REMOVE EXISTING MANUAL TRANSFER SWITCH. REPLACE WITH ATS.

B - 25-8391 Exhibit M_BID DRAWINGS_v9_FINAL_SS - page 9MOUNT NEW AUTOMATIC TRANSFER SWITCH TO EXISTING CABINET.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 173Automatic transfer switches shall be applied as service entrance switches and provided with a service entrance label.

ATS Load Sequencing / Shedding

AIWhen more than one emergency branch is shown: Life Safety Branch - no time delay on transfer to emergency; Optional Standby Branch - transfers after life safety branch has transferred and generator recovered to 90% rated voltage and frequency. Time delay adjustable 1-300 seconds.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1732. Optional Standy Branch - shall transfer to emergency after the life safety branch has transferred to emergency and generator has recovered to 90% of rated voltage and frequency.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 1731. Life Safety Branch - no time delay on transfer to emergency.

C - 25-8391 Exhibit M_BID SPECIFICATIONS_v9_FINAL_SS - page 173When more than one emergency branch is shown, time delay relays shall be provided on the transfer to emergency operation for critical and equipment branch transfer switches.

Reviewer verdict & notesdraft
Source DocumentsSource Page
PDF
PO_Terms_and_Conditions_Rev.3.pdf
DOC
25-8391_Bid_Schedule.xlsx
PDF
25-8391_-_Authorization_to_Advertise_FE.pdf
PDF
25-8391_Exhibit_M_BID_SPECIFICATIONS_v9_FINAL_SS.pdf
PDF
25-8391_-_Solicitation.pdf
PDF
25-8391_SPP.pdf
PDF
25-8391_Exhibit_N_-_EHS_Contractor_Requirements_Master_2021_rev.pdf
PDF
25-8391_Exhibit_M_BID_DRAWINGS_v9_FINAL_SS.pdf
PDF
Construction_Bid_Instructions_Version_1.pdf
PDF
Construction_Services_Agreement_2025_Template_ver_3_with_Exhibits.pdf
PDF
25-8391_Pre-Bid_Meeting_06.26.26.pdf
PDF
25-8391_Supplemental_Qualifications_v3.pdf