Past due priced

ROC Generator

The submission deadline has passed; pricing is retained for history.

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmReview
Project LocationEllington Field, Houston, Texas (Building 1191)Meets
Fuel TypeDieselMeets
Size (kW) + QuantityLine 1: 1 × 350 kW · diesel · 277/480V, 3 PH · permanentMeets
Send to distributorEvidence packet attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Evidence Packet - ROC Generator - Due Jul 3, 2026
AttachmentROC Generator.pdf
[DISTRIBUTOR NAME], We have a bid opportunity in Houston, TX that fits your coverage area. Details below. Opportunity: ROC Generator Contracting Agency: DEPT OF DEFENSE.DEPT OF THE ARMY.NATIONAL GUARD BUREAU.JFHQ USPFO TX.USPFO TX PROCUREMENT.W7N2 USPFO ACTIVITY TXANG 147 Location: Houston, TX Due Date: Jul 3, 2026 Key Specs: 1 × PD350-01 The evidence packet is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Past due priced
Bid value
$52,809.60
Checks reviewed
0/51 reviewed
Provisional pricing0.48

A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. The submission deadline has passed; pricing is retained for history.

Found value

$110,020.00

Configurator/list/base price
$110,020.00
Active manual adders
$0.00
Reviewed list/base price
$110,020.00
Distributor net
$52,809.60
1 × PD350-01
350 kW · diesel · $110,020.00
Distributor multiplierControls reviewed net pricing
New manual adderSaved as active reviewer pricing provenance
Active on save
No manual pricing adders have been saved.
Packet regenerationNo generated packet is recorded.
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AI

No source-backed value found

Project Location

AIEllington Field, Houston, Texas (Building 1191)

1. W50S7726RA001 - ROC Genrator.pdf - page 1PROJECT LOCATION: ELLINGTON FIELD AB, HOUSTON TX

2. SOW - ROC Generator.pdf - page 2Contractor shall perform all work on Ellington Field, in Houston Texas

Project Application

AIEmergency standby power for Building 1191 (147th Operations Group), a 24-hour continuous-operations facility requiring non-interruptible capabilities

2. SOW - ROC Generator.pdf - page 1emergency standby generator system supporting Building 1191, a 24-hour facility supporting continuous non- interruptible capabilities

2. SOW - ROC Generator.pdf - page 2The 147th Operations Group operates 24-hours from Building 1191.

Generator Requirements35
Rating Type / Application

AI

2. SOW - ROC Generator.pdf - page 1emergency standby generator system

Fuel TypePricing input

AIDiesel

2. SOW - ROC Generator.pdf - page 4Tier 3 diesel fuel engine-driven genset

2. SOW - ROC Generator.pdf - page 1new 350KW diesel (350 KW 277/480V 3 phase, 60 Hz.)

Size (kW) + QuantityPricing input

AILine 1: 1 × 350 kW · diesel · 277/480V, 3 PH · permanent

2. SOW - ROC Generator.pdf - page 1new 350KW diesel (350 KW 277/480V 3 phase, 60 Hz.) emergency standby generator system

2. SOW - ROC Generator.pdf - page 3The Contractor shall procure one (1) complete diesel standby generator system

Voltage + PhasePricing input

AIphase: 3 · voltage: 277/480V

2. SOW - ROC Generator.pdf - page 4277/480V • 3-Phase • 60Hz

2. SOW - ROC Generator.pdf - page 1350 KW 277/480V 3 phase, 60 Hz.

Alternator Rating / Temp Rise

AI

2. SOW - ROC Generator.pdf - page 4Alternator

Voltage Regulator

AI

No source-backed value found

Generator Space Heater

AI

No source-backed value found

Control Panel

AIBasler 2020 controller; digital control system

2. SOW - ROC Generator.pdf - page 4Basler 2020 controller

2. SOW - ROC Generator.pdf - page 4Digital control system

Control Panel Options / Accessories

AIEmergency shutdown system; remote annunciation capability

2. SOW - ROC Generator.pdf - page 4Remote annunciation capability

2. SOW - ROC Generator.pdf - page 4Emergency shutdown system

Remote Annunciator

AIRemote annunciation capability (verification required)

2. SOW - ROC Generator.pdf - page 8Remote annunciation verification

2. SOW - ROC Generator.pdf - page 4Remote annunciation capability

Enclosure Type + Material

AIWeather-protected aluminum enclosure; 200 MPH wind-rated

2. SOW - ROC Generator.pdf - page 4200 MPH wind-rated enclosure

2. SOW - ROC Generator.pdf - page 4Weather-protected aluminum enclosure

Sound Attenuation

AILevel 2 sound attenuated enclosure

2. SOW - ROC Generator.pdf - page 2weatherproof/sound attenuated enclosure generator

2. SOW - ROC Generator.pdf - page 4Level 2 sound attenuated enclosure

Enclosure / Auxiliary-Power Accessories

AI

No source-backed value found

Circuit Breaker(s)

AIMainline circuit breaker

2. SOW - ROC Generator.pdf - page 4Mainline circuit breaker

Generator Circuit Breaker

AIMainline circuit breaker

2. SOW - ROC Generator.pdf - page 4Mainline circuit breaker

Engine Filters

AI

No source-backed value found

EPSS Class / Level

AI

2. SOW - ROC Generator.pdf - page 2NFPA 110 standard for the 4-hour load bank test

Exhaust Connector End Fittings

AI

No source-backed value found

Generator Control Alarms

AIEmergency shutdown system; generator protective shutdown; alarm testing/verification required

2. SOW - ROC Generator.pdf - page 4Emergency shutdown system

2. SOW - ROC Generator.pdf - page 8Generator protective shutdown testing

Generator Breaker Settings / Trip

AI

2. SOW - ROC Generator.pdf - page 5Verify breaker coordination

2. SOW - ROC Generator.pdf - page 7Breaker setting verification

Vibration Isolators

AI

2. SOW - ROC Generator.pdf - page 5Verify vibration isolation requirements

Voltage / Frequency Transient Testing

AI

2. SOW - ROC Generator.pdf - page 8Frequency stability testing

2. SOW - ROC Generator.pdf - page 7Voltage regulation testing

Battery Compartment Heater

AI

No source-backed value found

Drawing Generator Rating / One-Line

AI

No source-backed value found

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AI

No source-backed value found

Jacket Water Heater

AIEngine coolant heater

2. SOW - ROC Generator.pdf - page 4Engine coolant heater

Exhaust Silencer

AICritical grade muffler

2. SOW - ROC Generator.pdf - page 4Critical grade muffler

Battery and Battery Charger

AIBattery charger; battery rack and cables

2. SOW - ROC Generator.pdf - page 4Battery rack and cables

2. SOW - ROC Generator.pdf - page 4Battery charger

Fuel Tank + Accessories

AI

2. SOW - ROC Generator.pdf - page 4Integral leak detection system

2. SOW - ROC Generator.pdf - page 4Fuel level monitoring system

2. SOW - ROC Generator.pdf - page 5UL142 double-wall fuel tank • Secondary containment

Factory Testing

AIFAT required prior to shipment: generator operational testing, voltage regulation testing, frequency regulation testing, protective device testing, control system testing, alarm testing, functional operational testing, manufacturer certification documentation; manufacturer-certified operational testing; factory startup support

2. SOW - ROC Generator.pdf - page 5Manufacturer-certified operational testing

2. SOW - ROC Generator.pdf - page 4Factory startup support

2. SOW - ROC Generator.pdf - page 7Factory testing shall include: • Generator operational testing • Voltage regulation testing • Frequency regulation testing • Protective device testing • Control system testing • Alarm testing • Functional operational testing •

Field Quality Control / Site Acceptance

AIInstallation verification testing (torque verification, megger, ground resistance, phase rotation, voltage, feeder continuity, insulation resistance, neutral verification, grounding/bonding, breaker setting, fuel leak, fuel level, alarm, battery, battery charger, heater, cooling); grounding/bonding testing; ATS testing (utility loss simulation, transfer, re-transfer, bypass, open/closed transition, time delay, sequence, alarms, remote annunciation); functional performance testing; NFPA 110 four-hour load bank test; infrared thermography; commissioning

2. SOW - ROC Generator.pdf - page 76.4 Automatic Transfer Switch (ATS) Testing

2. SOW - ROC Generator.pdf - page 76.2 Installation Verification Testing

2. SOW - ROC Generator.pdf - page 96.8 Commissioning Requirements

Load Bank

AIMinimum four-hour NFPA 110 load bank test; step loading; full-load operational testing; temporary load banks provided by contractor

2. SOW - ROC Generator.pdf - page 8Minimum four-hour load bank test

2. SOW - ROC Generator.pdf - page 8Full-load operational testing

2. SOW - ROC Generator.pdf - page 7temporary load banks

Switchgear / Paralleling

AI

No source-backed value found

Warranty

AI

No source-backed value found

Generator Overload Capacity

AI

No source-backed value found

ATS Requirements13
ATS Quantity

AIquantity: 1 · required: No · instances: tag: — · rating: —

2. SOW - ROC Generator.pdf - page 2Contractor to verify compatibility of existing Automatic Transfer Switch (ATS) with new generator controls

ATS Manufacturer / Model

AI

No source-backed value found

ATS Ratings

AI

2. SOW - ROC Generator.pdf - page 5Verify withstand ratings • Verify short circuit ratings

Transition Type

AIOpen transition; closed transition (if applicable)

2. SOW - ROC Generator.pdf - page 8Closed transition verification (if applicable)

2. SOW - ROC Generator.pdf - page 8Open transition verification

2. SOW - ROC Generator.pdf - page 2open/closed transition

Poles / Neutral Configuration

AI

No source-backed value found

ATS Enclosure Type

AI

No source-backed value found

ATS Features / Accessories

AIBypass/isolation requirements; manual bypass

2. SOW - ROC Generator.pdf - page 8Manual bypass testing

2. SOW - ROC Generator.pdf - page 2bypass/isolation requirements

ATS Transfer Timing

AI

2. SOW - ROC Generator.pdf - page 8Time delay verification

ATS Auxiliary Contacts

AI

No source-backed value found

ATS In-Phase Monitor

AI

No source-backed value found

ATS Engine Exerciser

AI

No source-backed value found

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AI

No source-backed value found

ATS Load Sequencing / Shedding

AI

2. SOW - ROC Generator.pdf - page 8Sequence of operation verification

Reviewer verdict & notesdraft
Source DocumentsSource Page
DOC
2.+SOW+-+ROC+Generator.pdf
DOC
3.+DBA+-+WD.pdf
DOC
1.+W50S7726RA001+-+ROC+Genrator.pdf
DOC
4.+Site+visit+-+FAR+52.236-27+-+ROC+Generator.pdf