AI—
No source-backed value found
| Field Check | Found Value | Status |
|---|---|---|
| Engineering Firm | — | Review |
| Project Location | Douglasville, GA 30134 | Meets |
| Fuel Type | Diesel | Meets |
| Size (kW) + Quantity | Line 1: 1 × 100 kW · diesel · 277/480V, 3 PH · permanent | Meets |
$68,545.00
AI—
No source-backed value found
AIDouglasville, GA 30134
Fleet Generator RFP Draft.pdf - page 18480 DORRIS RD DOUGLASVILLE,GA 30134
AIFleet Maintenance Building
Fleet Generator RFP Draft.pdf - page 3The Fleet Maintenance Building serves all Douglas County Departments daily and is home to numerous county employees.
AIStandby; NFPA 110, Level 1, Type 10
Fleet Generator RFP Draft.pdf - page 17NFPA 110, Level 1, Type 10 (10-second start time)
Fleet Generator RFP Draft.pdf - page 3100kW Diesel Standby Generator
AIDiesel
Fleet Generator RFP Draft.pdf - page 3100kW Diesel Standby Generator
AILine 1: 1 × 100 kW · diesel · 277/480V, 3 PH · permanent
Fleet Generator RFP Draft.pdf - page 17factory-assembled 100kW diesel engine-driven generator set
Fleet Generator RFP Draft.pdf - page 17100kW/125kVA at 0.8 power factor.
AIphase: 3 · voltage: 277/480V
Fleet Generator RFP Draft.pdf - page 17277/480V, 3-phase, 4-wire, 60Hz
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AINFPA 110 compliant digital controller with AutoStart/stop and safety shutdowns (high coolant temp, low oil pressure, overspeed)
Fleet Generator RFP Draft.pdf - page 17NFPA 110 compliant digital controller with AutoStart/stop and safety shutdowns (high coolant temp, low oil pressure, overspeed).
AIIntegrated Ethernet Cellular gateway for remote status alerts (E-mail/SMS) and Modbus integration for Building Automation Systems
Fleet Generator RFP Draft.pdf - page 18Integrated Ethernet Cellular gateway for remote status alerts (E-mail/SMS) and Modbus integration for Building Automation Systems.
AI—
No source-backed value found
AILevel 2 Sound Attenuated (weatherproof) enclosure
Fleet Generator RFP Draft.pdf - page 17Level 2 Sound Attenuated (weatherproof) enclosure
AILevel 2 Sound Attenuated; maximum 72 dB(A) at 23 feet (7 meters) in a free field
Fleet Generator RFP Draft.pdf - page 17Level 2 Sound Attenuated (weatherproof) enclosure. Maximum sound pressure level shall not exceed 72 dB(A) at 23 feet (7 meters) in a free field.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AINFPA 110, Level 1, Type 10 (10-second start time)
Fleet Generator RFP Draft.pdf - page 17NFPA 110, Level 1, Type 10 (10-second start time)
AI—
No source-backed value found
AISafety shutdowns: high coolant temp, low oil pressure, overspeed; electronic "low fuel" and "leak detected" alarms
Fleet Generator RFP Draft.pdf - page 17safety shutdowns (high coolant temp, low oil pressure, overspeed)
Fleet Generator RFP Draft.pdf - page 17electronic "low fuel" and "leak detected" alarms
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI15 Amp, 12 Volt, 50/60 Hz battery charger; Genset Starting Battery 12VDC
Fleet Generator RFP Draft.pdf - page 17Genset Starting Battery 12VDC
Fleet Generator RFP Draft.pdf - page 1715 Amp, 12 Volt, 50/60 Hz battery charger
AI250-gallon, double walled, sub-base fuel tank; mechanical fuel gauge; electronic "low fuel" and "leak detected" alarms
Fleet Generator RFP Draft.pdf - page 17250-gallon, double walled, sub-base fuel tank
Fleet Generator RFP Draft.pdf - page 17mechanical fuel gauge, electronic "low fuel" and "leak detected" alarms
AI—
No source-backed value found
AICertificate of Compliance stating the installation meets all local seismic, wind-load, and NFPA 110 Level 1 standards
Fleet Generator RFP Draft.pdf - page 19Certificate of Compliance stating the installation meets all local seismic, wind-load, and NFPA 110 Level 1 standards as required by the grant's mitigation goals.
AI—
No source-backed value found
AI—
No source-backed value found
AI4-hour on-site response time for emergency warranty repairs
Fleet Generator RFP Draft.pdf - page 21guarantee a 4-hour on-site response time for emergency warranty repairs
AI—
No source-backed value found
AIquantity: 1 · required: Yes · instances: tag: — · rating: 400A, NEMA 3R
Fleet Generator RFP Draft.pdf - page 17Automatic Transfer Switch (ATS)
Fleet Generator RFP Draft.pdf - page 17400A, NEMA 3R
AI—
No source-backed value found
AI400A
Fleet Generator RFP Draft.pdf - page 17Rating: 400A, NEMA 3R
AI—
No source-backed value found
AI3 Pole
Fleet Generator RFP Draft.pdf - page 173 Pole, silver-alloy contacts, and microprocessor controlled
AINEMA 3R
Fleet Generator RFP Draft.pdf - page 17Rating: 400A, NEMA 3R
AIIn-phase monitor to prevent motor damage during transfer; programmable plant exerciser (with and without load); 15 Amp, 12 Volt, 50/60 Hz battery charger; Auxiliary Relay-Switch in Emergency Position 12VDC; Auxiliary Relay-Switch in Normal Position 12VDC; Genset Starting Battery 12VDC
Fleet Generator RFP Draft.pdf - page 17In-phase monitor to prevent motor damage during transfer: programmable plant exerciser (with and without load). 15 Amp, 12 Volt, 50/60 Hz battery charger, Auxiliary Relay-Switch in Emergency Position 12VDC, Auxiliary Relay-Switch in Normal
AI—
No source-backed value found
AIAuxiliary Relay-Switch in Emergency Position 12VDC; Auxiliary Relay-Switch in Normal Position 12VDC
Fleet Generator RFP Draft.pdf - page 17Auxiliary Relay-Switch in Emergency Position 12VDC, Auxiliary Relay-Switch in Normal Position 12VDC
AIIn-phase monitor to prevent motor damage during transfer
Fleet Generator RFP Draft.pdf - page 17In-phase monitor to prevent motor damage during transfer
AIProgrammable plant exerciser (with and without load)
Fleet Generator RFP Draft.pdf - page 17programmable plant exerciser (with and without load)
AI—
No source-backed value found
AI—
No source-backed value found