FIRE STATION 7 GENERATOR REPLACEMENT

The submission deadline has passed; pricing is retained for history.

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmKluber Architects + EngineersMeets
Project Location1380 Aurora Avenue, Naperville, Illinois 60540Meets
Fuel TypeDieselMeets
Size (kW) + QuantityLine 1: 1 × 150 kW · diesel · 208Y/120, 3 PH · permanent; Line 2: 1 × 75 kW · diesel · temporaryMeets
Send to distributorEvidence packet attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Evidence Packet - FIRE STATION 7 GENERATOR REPLACEMENT - Due Jul 7, 2026
AttachmentFIRE STATION 7 GENERATOR REPLACEMENT.pdf
[DISTRIBUTOR NAME], We have a bid opportunity in Naperville, IL that fits your coverage area. Details below. Opportunity: FIRE STATION 7 GENERATOR REPLACEMENT Contracting Agency: City of Naperville, IL Location: Naperville, IL Due Date: Jul 7, 2026 Key Specs: 1 × JD150-01 The evidence packet is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Past due priced
Bid value
$40,084.80
Checks reviewed
0/51 reviewed
Provisional pricing0.48

A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. The submission deadline has passed; pricing is retained for history.

Found value

$83,510.00

Configurator/list/base price
$83,510.00
Active manual adders
$0.00
Reviewed list/base price
$83,510.00
Distributor net
$40,084.80
1 × JD150-01
150 kW · diesel · $83,510.00
1 × temporary
75 kW · diesel · Not charged
Distributor multiplierControls reviewed net pricing
New manual adderSaved as active reviewer pricing provenance
Active on save
No manual pricing adders have been saved.
Packet regenerationNo generated packet is recorded.
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AIKluber Architects + Engineers

A - Detailed Specifications - Fire Station 7 EM Generator - page 2ARCHITECT / ENGINEER KLUBER ARCHITECTS + ENGINEERS 41 W. BENTON STREET AURORA, ILLINOIS 60506

Project Location

AI1380 Aurora Avenue, Naperville, Illinois 60540

A - Detailed Specifications - Fire Station 7 EM Generator - page 2FIRE STATION #7 EM GENERATOR 1380 AURORA AVENUE NAPERVILLE, ILLINOIS 60540

Project Application

AIFire Station emergency/standby power

A - Detailed Specifications - Fire Station 7 EM Generator - page 7Project Name: FIRE STATION #7 EM GENERATOR.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1051. Application: Emergency/standby.

Generator Requirements35
Rating Type / Application

AIStandby, Emergency/standby

A - Detailed Specifications - Fire Station 7 EM Generator - page 1052. Power Rating: 150 kW, standby.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1051. Application: Emergency/standby.

Fuel TypePricing input

AIDiesel

A - Detailed Specifications - Fire Station 7 EM Generator - page 1051. Type: Diesel (compression ignition).

A - Detailed Specifications - Fire Station 7 EM Generator - page 107Fuel Source: Diesel, ASTM D975 No. 2-D or approved cold weather diesel blends.

Size (kW) + QuantityPricing input

AILine 1: 1 × 150 kW · diesel · 208Y/120, 3 PH · permanent; Line 2: 1 × 75 kW · diesel · temporary

A - Detailed Specifications - Fire Station 7 EM Generator - page 105Voltage: 208Y/120 V, 3 phase, 60 Hz.

A - Detailed Specifications - Fire Station 7 EM Generator - page 105Power Rating: 150 kW, standby.

A - Detailed Specifications - Fire Station 7 EM Generator - page 7Contractor to provide temporary 75kW diesel generator for duration of construction from start of demolition of existing generator until final acceptance of new generator set.

Voltage + PhasePricing input

AIphase: 3 · voltage: 208Y/120

A - Detailed Specifications - Fire Station 7 EM Generator - page 105Voltage: 208Y/120 V, 3 phase, 60 Hz.

Alternator Rating / Temp Rise

AIComply with UL 2200; Insulation System NEMA MG 00001, Class H

A - Detailed Specifications - Fire Station 7 EM Generator - page 109C. Temperature Rise: Comply with UL 2200.

A - Detailed Specifications - Fire Station 7 EM Generator - page 109D. Insulation System: NEMA MG 00001, Class H; suitable for alternator temperature rise.

Voltage Regulator

AIBrushless PMG excitation; generator-mounted volts per Hertz exciter-regulator; voltage regulation +/- one percent from no load to full load; PMG short-circuit current support 300 percent for 10 seconds

A - Detailed Specifications - Fire Station 7 EM Generator - page 1091. Exciter Type: Brushless; provide permanent magnet generator (PMG) excitation system; selfexcited (shunt) systems are not permitted.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1092. PMG Excitation Short-Circuit Current Support: Capable of sustaining 300 percent of rated output current for 10 seconds.

A - Detailed Specifications - Fire Station 7 EM Generator - page 109G. Voltage Regulation: Include generator-mounted volts per Hertz exciter-regulator to match engine and generator characteristics, with voltage regulation +/- one percent from no load to full load

Generator Space Heater

AI

No source-backed value found

Control Panel

AIMicroprocessor-based control system; unit-mounted, vibration isolated

A - Detailed Specifications - Fire Station 7 EM Generator - page 109A. Provide microprocessor-based control system for automatic control, monitoring, and protection of generator set.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1091. Control Panel Mounting: Unit-mounted unless otherwise indicated; vibration isolated.

Control Panel Options / Accessories

AIAutomatic/Manual/Reset/Emergency Stop modes; cycle cranking; programmable time delays; voltage adjustment +/-5%; push-to-test indicator lamps; 3-1/2 inch dial meters with phase selector switch for voltage and current; frequency, real power, reactive power, apparent power, power factor, duty level, engine speed, battery voltage, oil pressure, coolant temperature, run time indications; event log; remote monitoring via PC; auxiliary relay 3PDT; lamp test; common alarm contacts

A - Detailed Specifications - Fire Station 7 EM Generator - page 109a. Automatic Mode: Initiates generator set start/shutdown upon receiving corresponding signal from any automatic transfer switc (ATS1, ATS2 and ATS3).

A - Detailed Specifications - Fire Station 7 EM Generator - page 1115. Other Control Panel Features: a. Event log. b. Remote monitoring capability via PC.

A - Detailed Specifications - Fire Station 7 EM Generator - page 110i. Push-to-test indicator lamps, one each for low oil pressure, high water temperature, overspeed, and overcrank.

Remote Annunciator

AIWall-mounted; flush-mounted for finished areas, surface-mounted for non-finished areas; NFPA 110 indications; audible alarm with silence function; lamp test

A - Detailed Specifications - Fire Station 7 EM Generator - page 111b. Provide audible alarm with silence function.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1111. Remote Annunciator Mounting: Wall-mounted; Provide flush-mounted annunciator for finished areas and surface-mounted annunciator for non-finished areas unless otherwise indicated.

Enclosure Type + Material

AIAlternator enclosure: NEMA MG 00001, drip-proof

A - Detailed Specifications - Fire Station 7 EM Generator - page 109E. Enclosure: NEMA MG 00001, drip-proof.

Sound Attenuation

AICritical grade or better exhaust silencer; sound attenuation not less than basis of design; generator set sound level test data required

A - Detailed Specifications - Fire Station 7 EM Generator - page 103a. Include generator set sound level test data.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1093. Exhaust Silencer: Provide critical grade or better exhaust silencer with sound attenuation not less than basis of design

Enclosure / Auxiliary-Power Accessories

AI

No source-backed value found

Circuit Breaker(s)

AIMain line circuit breaker: thermal magnetic, NEMA AB 1 molded case, integral thermal and instantaneous magnetic trip in each pole, battery-voltage operated shunt trip; panelboard breakers UL 489; enclosed safety switches UL 98 heavy duty; fuses Class RK1 time-delay

A - Detailed Specifications - Fire Station 7 EM Generator - page 1054. Main Line Circuit Breaker: a. Type: Thermal magnetic.

A - Detailed Specifications - Fire Station 7 EM Generator - page 106a. NEMA AB 1 molded case circuit breaker on generator output with integral thermal and instantaneous magnetic trip in each pole; sized in accordance with ANSI/NFPA 70. Include battery-voltage operated shunt trip, connection to open circuit

Generator Circuit Breaker

AIThermal magnetic; NEMA AB 1 molded case; integral thermal and instantaneous magnetic trip in each pole; battery-voltage operated shunt trip; factory-installed line side connections; mounted in enclosure to meet ANSI/NEMA 250

A - Detailed Specifications - Fire Station 7 EM Generator - page 1054. Main Line Circuit Breaker: a. Type: Thermal magnetic.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1066. Main Line Circuit Breakers: Provide factory-installed line side connections with suitable lugs for load side connections. a. NEMA AB 1 molded case circuit breaker on generator output with integral thermal and instantaneous magnetic trip

Engine Filters

AILube oil filter, intake air filter (replaceable dry element), fuel filter(s) with water separator; two additional sets of each fuel, oil, and air filter element required for maintenance

A - Detailed Specifications - Fire Station 7 EM Generator - page 104c. Provide two additional sets of each fuel, oil, and air filter element required for the engine generator system.

A - Detailed Specifications - Fire Station 7 EM Generator - page 107Engine Fuel Supply: Provide engine-driven, positive displacement fuel pump with replaceable fuel filter(s), water separator

A - Detailed Specifications - Fire Station 7 EM Generator - page 106J. Engine Accessories: Lube oil filter, intake air filter, lube oil cooler, gear-driven water pump.

EPSS Class / Level

AINFPA 110 Level 1, Type 10

A - Detailed Specifications - Fire Station 7 EM Generator - page 1063. Start Time: Capable of starting and achieving conditions necessary for load acceptance within 10 seconds (NFPA 110, Type 10).

A - Detailed Specifications - Fire Station 7 EM Generator - page 1042. NFPA 110 (Standard for Emergency and Standby Power Systems); meet requirements for Level 1 system.

Exhaust Connector End Fittings

AIFlexible connector (approved) for coupling engine to exhaust system; flanged multiple corrugated stainless steel multi-ply expansion joints with liners; Class 150 slip-on forged steel flanges per ASME B16.5; ASTM A181 Grade I; ASME B16.21 composition ring gaskets

A - Detailed Specifications - Fire Station 7 EM Generator - page 77B. Flexible joints: 1. Provide flanged, multiple, corrugated, stainless steel (multi-ply) expansion joints with liners between exhaust manifold and exhaust piping to absorb thermal expansion and vibration.

A - Detailed Specifications - Fire Station 7 EM Generator - page 771) Class 150, slip-on, forged steel welding flanges in accordance with ASME B16.5.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1082. Engine Exhaust Connection: Provide suitable, approved flexible connector for coupling engine to exhaust system.

Generator Control Alarms

AIOvercrank (shutdown); low coolant temperature (warning); high coolant temperature (warning and shutdown); low oil pressure (warning and shutdown); overspeed (shutdown); low fuel level (warning); low coolant level (warning/shutdown); generator control not in automatic (warning); high/low battery voltage (warning); low cranking voltage (warning); battery charger failure (warning); high/low AC voltage (shutdown); high/low frequency (shutdown); overcurrent (shutdown); local and remote common alarm contacts

A - Detailed Specifications - Fire Station 7 EM Generator - page 1101) Overcrank (shutdown). 2) Low coolant temperature (warning). 3) High coolant temperature (warning). 4) High coolant temperature (shutdown). 5) Low oil pressure (warning). 6) Low oil pressure (shutdown). 7) Overspeed (shutdown).

A - Detailed Specifications - Fire Station 7 EM Generator - page 1115) Overcurrent (shutdown). c. Provide contacts for local and remote common alarm.

Generator Breaker Settings / Trip

AITrip rating: select according to generator set rating; integral thermal and instantaneous magnetic trip in each pole; battery-voltage operated shunt trip to open on engine failure; sized per ANSI/NFPA 70

A - Detailed Specifications - Fire Station 7 EM Generator - page 106b. Trip Rating: Select according to generator set rating.

A - Detailed Specifications - Fire Station 7 EM Generator - page 106a. NEMA AB 1 molded case circuit breaker on generator output with integral thermal and instantaneous magnetic trip in each pole; sized in accordance with ANSI/NFPA 70. Include battery-voltage operated shunt trip, connection to open circuit

Vibration Isolators

AISpring-type vibration isolators; mounted on structural steel base and concrete pad; spring isolators also for exhaust silencer

B - Drawings - Fire Station 7 EM Generator - page 2202 INSTALL SILENCER FOR ENGINE EXHAUST. SILENCER FURNISHED BY GENERATOR MANUFACTURER. PROVIDE WITH 3. 202 INSTALL SILENCER FOR ENGINE EXHAUST. SILENCER FURNISHED BY GENERATOR MANUFACTURER. PROVIDE WITH SPRING ISOLATORS.

A - Detailed Specifications - Fire Station 7 EM Generator - page 106L. Mounting: Provide unit with suitable spring-type vibration isolators and mount on structural steel base and concrete pad.

Voltage / Frequency Transient Testing

AIFactory: transient and steady state voltage and frequency performance tested. Field: voltage and frequency verified during load tests per NFPA 110 (1.5 hour building load test + 2 hour full load test); recordings at 20-minute intervals of kW, amps, voltage, coolant temp, room temp, oil pressure, frequency

A - Detailed Specifications - Fire Station 7 EM Generator - page 1136. Perform load tests in accordance with NFPA 110 (1.5 hour building load test followed by 2 hour full load test). a. During test, record the following at 20 minute intervals: 1) Kilowatts. 2) Amperes. 3) Voltage. 4) Coolant temperature. 5)

A - Detailed Specifications - Fire Station 7 EM Generator - page 1113. Transient and steady state voltage and frequency performance.

Battery Compartment Heater

AI

No source-backed value found

Drawing Generator Rating / One-Line

AI

A - Detailed Specifications - Fire Station 7 EM Generator - page 6E600 ELECTRICAL SINGLE LINE DIAGRAM

B - Drawings - Fire Station 7 EM Generator - page 4REFER TO SINGLE LINE, SHEET E800

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AI

B - Drawings - Fire Station 7 EM Generator - page 4REFER TO SINGLE LINE, SHEET E800

Jacket Water Heater

AIEngine mounted, thermostatically controlled, water jacket heater; sized as recommended by equipment supplier; heater voltage as required

A - Detailed Specifications - Fire Station 7 EM Generator - page 106K. Coolant heater: Engine mounted, thermostatically controlled, water jacket heater. The heater shall be sized as recommended by the equipment supplier. Heater voltage shall be as required.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1083. Coolant Heater: Provide thermostatically controlled coolant heater to improve starting under cold ambient conditions

Exhaust Silencer

AICritical grade or better; sound attenuation not less than basis of design; furnished by generator manufacturer; select per manufacturer recommendations

A - Detailed Specifications - Fire Station 7 EM Generator - page 1093. Exhaust Silencer: Provide critical grade or better exhaust silencer with sound attenuation not less than basis of design; select according to manufacturer's recommendations to meet sound performance requirements, where specified.

B - Drawings - Fire Station 7 EM Generator - page 2SILENCER FURNISHED BY GENERATOR MANUFACTURER.

Battery and Battery Charger

AIDual rate battery charger, automatic float and equalize modes, minimum 10 amps; UL 1236 listed; integral overcurrent protection; current limited during cranking; reverse polarity protection; integral DC ammeter and voltmeter; alarm output contacts; trickle type; battery type: lead-acid; battery rack, cables, connectors provided

A - Detailed Specifications - Fire Station 7 EM Generator - page 107a. Battery Type: Lead-acid.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1084. Battery Charger: a. Provide dual rate battery charger with automatic float and equalize charging modes and minimum rating of 10 amps

A - Detailed Specifications - Fire Station 7 EM Generator - page 108c. Listed as complying with UL 1236.

Fuel Tank + Accessories

AISeparately mounted double-wall day tank with secondary containment; UL 142 listed; fuel transfer pump(s), valves, automatic controls; compatible with existing Tramont System 2000 ECM; capacity for minimum 4 hours at 100% rated load; alarms: low fuel level, critical low fuel level, high fuel level, critical high fuel level; direct reading fuel level gauge; normal atmospheric vent; emergency pressure relief vent; reuse existing underground fuel tank

A - Detailed Specifications - Fire Station 7 EM Generator - page 1071) Compatible with existing fuel storage system: Tramont System 2000 ECM with day tank demand.

A - Detailed Specifications - Fire Station 7 EM Generator - page 107Reuse existing underground fuel tank from existing generator.

A - Detailed Specifications - Fire Station 7 EM Generator - page 107a. Provide separately mounted double-wall day tank with secondary containment, with fuel transfer pump(s), valves, and automatic controls suitable for operation in the configuration to be installed; listed and labeled as complying with UL 1

Factory Testing

AIProduction tests at factory: operation at rated load and rated power factor; single step load pick-up; transient and steady state voltage and frequency performance; operation of safety shutdowns; certified test report included with submittals

A - Detailed Specifications - Fire Station 7 EM Generator - page 111B. Perform production tests on generator sets at factory to verify operation and performance characteristics prior to shipment. Include certified test report with submittals.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1111. Operation at rated load and rated power factor. 2. Single step load pick-up. 3. Transient and steady state voltage and frequency performance. 4. Operation of safety shutdowns.

Field Quality Control / Site Acceptance

AIAcceptance test per NFPA 110; 1.5 hour building load test followed by 2 hour full load test; recordings at 20-minute intervals; verify starting/load acceptance, voltage, frequency, phase sequence, control system, safety shutdowns, auxiliary equipment; test alarm and shutdown circuits by simulation; NETA ATS inspection for ATS; ground resistance max 5 ohms; manufacturer's representative required for start-up

A - Detailed Specifications - Fire Station 7 EM Generator - page 113G. Perform acceptance test in accordance with NFPA 110.

A - Detailed Specifications - Fire Station 7 EM Generator - page 113b. Test alarm and shutdown circuits by simulating conditions.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1136. Perform load tests in accordance with NFPA 110 (1.5 hour building load test followed by 2 hour full load test).

Load Bank

AIExisting permanent load bank salvaged to owner; new dual purpose docking station for portable generator and load bank connection provided; load bank and fuel provided by contractor for field testing

B - Drawings - Fire Station 7 EM Generator - page 4SALVAGE EXISTING PERMANENT LOAD BANK AND TURN OVER TO OWNER. DEMOLISH ALL ASSOCIATED FEEDERS AND CONTROLLERS BACK TO SOURCE.

A - Detailed Specifications - Fire Station 7 EM Generator - page 113D. Provide all equipment, tools, and supplies required to accomplish inspection and testing, including load bank and fuel.

B - Drawings - Fire Station 7 EM Generator - page 4PROVIDE NEW DUAL PURPOSE DOCKING STATION FOR PORTABLE GENERATOR AND LOADBANK CONNECTION, REFER TO SPECIFICATIONS.

Switchgear / Paralleling

AISingle packaged engine generator set operated independently (not in parallel)

A - Detailed Specifications - Fire Station 7 EM Generator - page 1052. Configuration: Single packaged engine generator set operated independently (not in parallel).

Warranty

AIMinimum one year manufacturer warranty covering repair or replacement due to defective materials or workmanship; one year contractor guarantee from date of final acceptance and final payment; one year service and maintenance of generator system

FIRE_STATION_7_GENERATOR_REPLACEMENT_(Addendum_#1_Revision).pdf - page 25the Contractor shall unconditionally guarantee the materials and workmanship on all materials, items and work furnished under this contract, including contract changes and additions FOR A PERIOD OF ONE YEAR from date of final acceptance and

A - Detailed Specifications - Fire Station 7 EM Generator - page 105B. Provide minimum one year manufacturer warranty covering repair or replacement due to defective materials or workmanship.

Generator Overload Capacity

AIPMG excitation short-circuit current support: 300 percent of rated output current for 10 seconds; maximum load step: 100 percent of rated load in one step

A - Detailed Specifications - Fire Station 7 EM Generator - page 1092. PMG Excitation Short-Circuit Current Support: Capable of sustaining 300 percent of rated output current for 10 seconds.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1064. Maximum Load Step: Supports 100 percent of rated load in one step.

ATS Requirements13
ATS Quantity

AIquantity: 3 · required: Yes · instances: tag: ATS1 · rating: —; tag: ATS2 · rating: —; tag: ATS3 · rating: —

A - Detailed Specifications - Fire Station 7 EM Generator - page 1211. ATS1: Transfer within 10 seconds 2. ATS2 and ATS3: Transfer within 1 minute. 3. ATS3 (ELEVATOR TEST MODE): Transfer within 10 seconds.

A - Detailed Specifications - Fire Station 7 EM Generator - page 109a. Automatic Mode: Initiates generator set start/shutdown upon receiving corresponding signal from any automatic transfer switc (ATS1, ATS2 and ATS3).

B - Drawings - Fire Station 7 EM Generator - page 4PROVIDE NEW ATS-1, COORDINATE CONSTRUCTION WITH OWNER TO LIMIT DOWNTIME, REFER TO SINGLE LINE FOR MORE INFORMATION.

ATS Manufacturer / Model

AIBasis of Design: Schneider Electric; ASCO 7000 Series. Other acceptable: ABB, Eaton, Generac, Rehlko

A - Detailed Specifications - Fire Station 7 EM Generator - page 1171. ABB: www.electrification.us.abb.com/#sle. 2. Eaton Corporation: www.eaton.com/#sle. 3. Generac Power Systems: www.generac.com/industrial/#sle. 4. Rehlko: www.powersystems.rehlko.com/#sle. 5. Schneider Electric; ASCO Power Technologies: w

A - Detailed Specifications - Fire Station 7 EM Generator - page 117D. Basis of Design - Automatic Transfer Switch: Schneider Electric; ASCO 7000 Series:

ATS Ratings

AIFrame: 150 A to 600 A; Voltage: 208 V; Ampere Rating: as indicated on drawings

A - Detailed Specifications - Fire Station 7 EM Generator - page 118f. Voltage: 208 V.

A - Detailed Specifications - Fire Station 7 EM Generator - page 118e. Ampere Rating: As indicated on drawings.

A - Detailed Specifications - Fire Station 7 EM Generator - page 117a. Frame: 150 A to 600 A.

Transition Type

AIOpen transition

A - Detailed Specifications - Fire Station 7 EM Generator - page 117b. Transition Configuration: Open transition.

Poles / Neutral Configuration

AIThree phase poles; solid neutral

A - Detailed Specifications - Fire Station 7 EM Generator - page 117c. Neutral Configuration: Solid neutral.

A - Detailed Specifications - Fire Station 7 EM Generator - page 117d. Phase Poles: Three.

ATS Enclosure Type

AI

A - Detailed Specifications - Fire Station 7 EM Generator - page 121M. Enclosure: ICS 10, Type 1, finished with manufacturer's standard gray enamel.

ATS Features / Accessories

AIBypass/isolation switches (overlapping make-before-break); elevator test switch; three position selector switch (AUTO, OFF, TEST); indicating lights (NORMAL SOURCE AVAILABLE, ALTERNATE SOURCE AVAILABLE, SWITCH POSITION, NORMAL BYPASS, ALTERNATE SOURCE BYPASS); green lamp (normal), red lamp (emergency); frequency/voltage relay; disconnect plug on wiring harness; return to normal switch; normal source monitor; alternate source monitor; bypass/isolation operation (normal, test, isolate modes)

A - Detailed Specifications - Fire Station 7 EM Generator - page 120B. Elevator Test Switch: Mount in cover of enclosure to simulate failure of normal source.

A - Detailed Specifications - Fire Station 7 EM Generator - page 120A. Indicating Lights: Mount in cover of enclosure to indicate NORMAL SOURCE AVAILABLE, ALTERNATE SOURCE AVAILABLE, SWITCH POSITION, NORMAL BYPASS, and ALTERNATE SOURCE BYPASS.

A - Detailed Specifications - Fire Station 7 EM Generator - page 1182. Bypass/Isolation Switch Type: Provide overlapping (make-before-break) switches with no interruption of power to load.

ATS Transfer Timing

AIATS1: transfer within 10 seconds; ATS2 and ATS3: transfer within 1 minute; ATS3 elevator test mode: transfer within 10 seconds; time delay to start engine generator: 0-10 seconds adjustable; time delay before transfer to alternate: 0-60 seconds adjustable; time delay before transfer to normal: 0-30 minutes adjustable; time delay before engine shutdown: 0-30 minutes adjustable

A - Detailed Specifications - Fire Station 7 EM Generator - page 1211. ATS1: Transfer within 10 seconds 2. ATS2 and ATS3: Transfer within 1 minute. 3. ATS3 (ELEVATOR TEST MODE): Transfer within 10 seconds.

A - Detailed Specifications - Fire Station 7 EM Generator - page 121B. Time Delay To Start Alternate Source Engine Generator: 0 to 10 seconds, adjustable.

A - Detailed Specifications - Fire Station 7 EM Generator - page 121F. Time Delay Before Transfer to Normal Power: 0 to 30 minutes, adjustable; bypass time delay in event of alternate source failure.

ATS Auxiliary Contacts

AIMain shaft auxiliary contact rated 10 ampere at 240V (one closed on normal, one closed on emergency); transfer switch auxiliary contacts: 1 normally open, 1 normally closed

A - Detailed Specifications - Fire Station 7 EM Generator - page 120F. Main shaft auxiliary contact rated ten (10) ampere at 240V (one closed on normal and one closed on emergency).

A - Detailed Specifications - Fire Station 7 EM Generator - page 120H. Transfer Switch Auxiliary Contacts: 1 normally open; 1 normally closed.

ATS In-Phase Monitor

AIInphase monitor: permits transfer when phase voltages are within 15 degrees and two cycles; if source supplying load fails or drops below 70 percent, permits immediate transfer

A - Detailed Specifications - Fire Station 7 EM Generator - page 120K. Inphase Monitor: Monitors normal and emergency sources and permits transfer when phase voltages are 15 degrees and two (2) cycles. If the source supplying the load fails or drops below 70 percent, the monitor will permit immediate transf

ATS Engine Exerciser

AIStart engine every 7 days; run for 30 minutes before shutting down; bypass exerciser control if normal source fails during exercising period

A - Detailed Specifications - Fire Station 7 EM Generator - page 121H. Engine Exerciser: Start engine every 7 days; run for 30 minutes before shutting down. Bypass exerciser control if normal source fails during exercising period.

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AI

B - Drawings - Fire Station 7 EM Generator - page 4REFER TO SINGLE LINE, SHEET E800

ATS Load Sequencing / Shedding

AILoad shedding contacts (2 NO and 2 NC) operating from adjustable 0.6-60 seconds prior to transfer in either direction; resets 0.6-60 seconds after transfer

A - Detailed Specifications - Fire Station 7 EM Generator - page 121L. Load shedding contacts (2 NO and 2 NC) that operates from an adjustable 0.6 -60 seconds prior to transfer in either direction and resets .6 - 60 seconds after transfer.

Reviewer verdict & notesdraft
Source DocumentsSource Page
DOC
FS7_Generator_BID_WORKSHEET.xlsx
PDF
1651_-_Cost_-_CD_Detailed.pdf
PDF
1651_-_SPECS_-_City_of_Naperville_-_Fire_Station_7_EM_Generator.pdf
DOC
INSURANCE_SAMPLE.docx
PDF
1651_-_DWGS_-_City_of_Naperville_-_Fire_Station_7_EM_Generator.pdf
PDF
CONTRACTOR_SAFETY_ORIENTATION_CHECKLIST.pdf
DOC
FS7_Generator_Bid_Spec.docx
PDF
1651_-_SPECS_-_City_of_Naperville_-_Fire_Station_7_EM_Generator.pdf
PDF
FIRE_STATION_7_GENERATOR_REPLACEMENT_(Addendum_%231_Revision).pdf
PDF
Drawings_-_Fire_Station_7_EM_Generator.pdf
PDF
Writing_a_Scope_of_Work.pdf
PDF
Insurance_Sample.pdf