AI—
No source-backed value found
Resolve the submission deadline before treating this opportunity as active.
| Field Check | Found Value | Status |
|---|---|---|
| Engineering Firm | — | Review |
| Project Location | Rockford, Illinois | Meets |
| Fuel Type | Diesel | Meets |
| Size (kW) + Quantity | Line 1: 1 × 125 kW · diesel · 277/480V, 3 PH · permanent | Meets |
A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. Resolve the submission deadline before treating this opportunity as active.
$62,950.00
AI—
No source-backed value found
AIRockford, Illinois
Conklin ES - Electrical Drawings.pdf - page 2ROCKFORD, ILLINOIS
AISchool
Conklin ES - Electrical Drawings.pdf - page 1ROCKFORD PUBLIC SCHOOL DISTRICT 205
Conklin ES - Electrical Drawings.pdf - page 1CANDIDATE SCHOOL AT CONKLIN
AIStationary Emergency Standby
Gen Specs.pdf - page 4C. Power Rating: Stationary Emergency Standby
AIDiesel
Conklin ES - Electrical Drawings.pdf - page 1125 KW DIESEL GENERATOR
Gen Specs.pdf - page 5A. Fuel: ASTM D975, diesel fuel oil, Grade 2-D S15
AILine 1: 1 × 125 kW · diesel · 277/480V, 3 PH · permanent
Gen Specs.pdf - page 4I. Voltage: 480-V ac
Conklin ES - Electrical Drawings.pdf - page 1125 KW DIESEL GENERATOR
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 3PH, 4W
AIphase: 3 · voltage: 277/480V
Gen Specs.pdf - page 4I. Voltage: 480-V ac
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 3PH, 4W
Gen Specs.pdf - page 4J. Phase: Three-phase, four wire
AI—
Gen Specs.pdf - page 11K. Subtransient Reactance: 12 percent, maximum.
Gen Specs.pdf - page 11C. Electrical Insulation: Class H.
Gen Specs.pdf - page 11G. Enclosure: Dripproof.
AI—
Gen Specs.pdf - page 113. Provide anti-hunt provision to stabilize voltage.
Gen Specs.pdf - page 112. Maintain voltage within 15 percent on one step, full load.
Gen Specs.pdf - page 114. Maintain frequency within 5 percent and stabilize at rated frequency within 2 seconds.
AI—
No source-backed value found
AI—
ATS Specs.pdf - page 51. Power Command 40-11 control.
AI—
No source-backed value found
AI—
ATS Specs.pdf - page 5Remote Annunciator.
AI—
Gen Specs.pdf - page 12B. Structural Design and Anchorage: Comply with ASCE/SEI 7 for wind loads up to 100 mph.
AIMuffler/silencer: minimum sound attenuation of 25 dB at 500 Hz; sound level at 25 ft from exhaust discharge after installation shall be 78 dBA or less. Enclosure sound attenuation level: 1.
Gen Specs.pdf - page 12Sound Attenuation Level: 1
Gen Specs.pdf - page 6Minimum sound attenuation of 25 dB at 500 Hz.
Gen Specs.pdf - page 6shall be 78 dBA or less.
AI—
Gen Specs.pdf - page 12E. Muffler Location: External to enclosure.
Conklin ES - Electrical Drawings.pdf - page 1GENERATOR REMOTE
Gen Specs.pdf - page 12C. Hinged Doors: With locking provisions.
AI—
No source-backed value found
AI—
Gen Specs.pdf - page 10d. Mounting: Adjacent to, or integrated with, control and monitoring panel.
AI—
Gen Specs.pdf - page 3Filters: One set each of lubricating oil, fuel, and combustion-air filters.
AILevel 1, Type 10 per NFPA 110 (10-second start time)
Gen Specs.pdf - page 5b. 10 seconds.
Gen Specs.pdf - page 5Comply with NFPA 110, Type 10 system requirements.
Gen Specs.pdf - page 4E. EPSS Class: Engine generator shall be classified as a Level 1 according to NFPA 110.
AI—
Gen Specs.pdf - page 14A. Connect engine exhaust pipe to engine with flexible connector.
AI—
No source-backed value found
AI—
Gen Specs.pdf - page 10a. Tripping Characteristics: Adjustable long-time and short-time delay and instantaneous.
Gen Specs.pdf - page 10b. Trip Settings: Selected to coordinate with generator thermal damage curve.
AI—
Gen Specs.pdf - page 123. Minimum Additional Travel: 50 percent of required deflection at rated load.
Gen Specs.pdf - page 12A. Restrained Spring Isolators: Freestanding, steel, open-spring isolators.
Gen Specs.pdf - page 126. Minimum Deflection: 1 inch.
AI—
No source-backed value found
AI—
No source-backed value found
AIE112 one-line: GENERATOR, 277/480V, 3PH, 4W, 150 KVA. E103 drawing: IBCS-GEN-1, 125 KW DIESEL GENERATOR, 25 hours continuous run time.
Conklin ES - Electrical Drawings.pdf - page 1TO PROVIDE 25 HOURS OF
Conklin ES - Electrical Drawings.pdf - page 2GENERATOR
Conklin ES - Electrical Drawings.pdf - page 1IBCS-GEN-1
AIOn E112 one-line, breakers connected to generator bus: IBCS-ATS-EM — 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION; IBCS-ATS-X — 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Breakers 100/60 and 250/250 also appear near the generator/switchboard section of the one-line.
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 60A, 35kA
Conklin ES - Electrical Drawings.pdf - page 2250/250
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA
AI—
Gen Specs.pdf - page 6D. Jacket Coolant Heater: Electric-immersion type, factory installed in coolant jacket system.
AI—
Gen Specs.pdf - page 6Minimum sound attenuation of 25 dB at 500 Hz.
Gen Specs.pdf - page 6Sound level measured at a distance of 25 feet from exhaust discharge after installation
Gen Specs.pdf - page 6shall be 78 dBA or less.
AI—
No source-backed value found
AI—
Gen Specs.pdf - page 83. Leak detection in interstitial space.
Conklin ES - Electrical Drawings.pdf - page 1TO PROVIDE 25 HOURS OF
Gen Specs.pdf - page 85. Containment Provisions: Comply with requirements of authorities having jurisdiction.
AI—
Gen Specs.pdf - page 131. Tests: Comply with IEEE 115 and with NFPA 110, Level 1 Energy Converters.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
ATS Specs.pdf - page 21. Warranty Period: 12 months from date of Substantial Completion.
Gen Specs.pdf - page 31. Warranty Period: One year from date of Substantial Completion.
AI—
Gen Specs.pdf - page 4D. Overload Capacity: 110 percent of service load for 1 hour in 12 consecutive hours.
AIquantity: 2 · required: Yes · instances: tag: IBCS-ATS-EM · rating: 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION (E112 one-line); 60 AMP (E103); tag: IBCS-ATS-X · rating: 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION (E112 one-line); 200 AMP (E103)
Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-X
Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-EM
Conklin ES - Electrical Drawings.pdf - page 1IBCS-ATS-X" (200AMP)
AIASCO Power Technologies; Cummins Power Generation (Basis of Design) OTEC Series
ATS Specs.pdf - page 3ASCO Power Technologies.
ATS Specs.pdf - page 3Cummins Power Generation (Basis of Design) OTEC Series.
AI—
ATS Specs.pdf - page 21. Short-time withstand capability for 30 cycles.
ATS Specs.pdf - page 3B. Comply with Level 1 equipment according to NFPA 110.
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA
AI—
Conklin ES - Electrical Drawings.pdf - page 2OPEN TRANSITION
AI—
ATS Specs.pdf - page 2K. Neutral Terminal: Solid and fully rated.
Conklin ES - Electrical Drawings.pdf - page 23PH, 4W, 4 POLE
AI—
No source-backed value found
AI—
No source-backed value found
AI—
ATS Specs.pdf - page 4b. Time delay adjustable from zero to five minutes, and factory set for five minutes.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AIInstance 1 — Tag: IBCS-ATS-EM (E103 label: IBCS-ATM-EM); E103 rating: 60 AMP; E112 one-line rating: 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Instance 2 — Tag: IBCS-ATS-X; E103 rating: 200 AMP; E112 one-line rating: 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Note: E103 shows 200 AMP while E112 one-line shows 250A for IBCS-ATS-X.
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 60A, 35kA
Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA
Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-X
AI—
No source-backed value found