Due date missing

Conklin Elementary

Resolve the submission deadline before treating this opportunity as active.

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmReview
Project LocationRockford, IllinoisMeets
Fuel TypeDieselMeets
Size (kW) + QuantityLine 1: 1 × 125 kW · diesel · 277/480V, 3 PH · permanentMeets
Send to distributorEvidence packet attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Evidence Packet - Conklin Elementary - Due not listed
AttachmentConklin Elementary.pdf
[DISTRIBUTOR NAME], We have a bid opportunity in your territory that fits your coverage area. Details below. Opportunity: Conklin Elementary Contracting Agency: Conklin Elementary Due Date: not listed Key Specs: 1 × PD125-01 The evidence packet is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Due date missing
Bid value
$30,216.00
Checks reviewed
0/51 reviewed
Provisional pricing0.48

A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. Resolve the submission deadline before treating this opportunity as active.

Found value

$62,950.00

Configurator/list/base price
$62,950.00
Active manual adders
$0.00
Reviewed list/base price
$62,950.00
Distributor net
$30,216.00
1 × PD125-01
125 kW · diesel · $62,950.00
Distributor multiplierControls reviewed net pricing
New manual adderSaved as active reviewer pricing provenance
Active on save
No manual pricing adders have been saved.
Packet regenerationNo generated packet is recorded.
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AI

No source-backed value found

Project Location

AIRockford, Illinois

Conklin ES - Electrical Drawings.pdf - page 2ROCKFORD, ILLINOIS

Project Application

AISchool

Conklin ES - Electrical Drawings.pdf - page 1ROCKFORD PUBLIC SCHOOL DISTRICT 205

Conklin ES - Electrical Drawings.pdf - page 1CANDIDATE SCHOOL AT CONKLIN

Generator Requirements35
Rating Type / Application

AIStationary Emergency Standby

Gen Specs.pdf - page 4C. Power Rating: Stationary Emergency Standby

Fuel TypePricing input

AIDiesel

Conklin ES - Electrical Drawings.pdf - page 1125 KW DIESEL GENERATOR

Gen Specs.pdf - page 5A. Fuel: ASTM D975, diesel fuel oil, Grade 2-D S15

Size (kW) + QuantityPricing input

AILine 1: 1 × 125 kW · diesel · 277/480V, 3 PH · permanent

Gen Specs.pdf - page 4I. Voltage: 480-V ac

Conklin ES - Electrical Drawings.pdf - page 1125 KW DIESEL GENERATOR

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 3PH, 4W

Voltage + PhasePricing input

AIphase: 3 · voltage: 277/480V

Gen Specs.pdf - page 4I. Voltage: 480-V ac

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 3PH, 4W

Gen Specs.pdf - page 4J. Phase: Three-phase, four wire

Alternator Rating / Temp Rise

AI

Gen Specs.pdf - page 11K. Subtransient Reactance: 12 percent, maximum.

Gen Specs.pdf - page 11C. Electrical Insulation: Class H.

Gen Specs.pdf - page 11G. Enclosure: Dripproof.

Voltage Regulator

AI

Gen Specs.pdf - page 113. Provide anti-hunt provision to stabilize voltage.

Gen Specs.pdf - page 112. Maintain voltage within 15 percent on one step, full load.

Gen Specs.pdf - page 114. Maintain frequency within 5 percent and stabilize at rated frequency within 2 seconds.

Generator Space Heater

AI

No source-backed value found

Control Panel

AI

ATS Specs.pdf - page 51. Power Command 40-11 control.

Control Panel Options / Accessories

AI

No source-backed value found

Remote Annunciator

AI

ATS Specs.pdf - page 5Remote Annunciator.

Enclosure Type + Material

AI

Gen Specs.pdf - page 12B. Structural Design and Anchorage: Comply with ASCE/SEI 7 for wind loads up to 100 mph.

Sound Attenuation

AIMuffler/silencer: minimum sound attenuation of 25 dB at 500 Hz; sound level at 25 ft from exhaust discharge after installation shall be 78 dBA or less. Enclosure sound attenuation level: 1.

Gen Specs.pdf - page 12Sound Attenuation Level: 1

Gen Specs.pdf - page 6Minimum sound attenuation of 25 dB at 500 Hz.

Gen Specs.pdf - page 6shall be 78 dBA or less.

Enclosure / Auxiliary-Power Accessories

AI

Gen Specs.pdf - page 12E. Muffler Location: External to enclosure.

Conklin ES - Electrical Drawings.pdf - page 1GENERATOR REMOTE

Gen Specs.pdf - page 12C. Hinged Doors: With locking provisions.

Circuit Breaker(s)

AI

No source-backed value found

Generator Circuit Breaker

AI

Gen Specs.pdf - page 10d. Mounting: Adjacent to, or integrated with, control and monitoring panel.

Engine Filters

AI

Gen Specs.pdf - page 3Filters: One set each of lubricating oil, fuel, and combustion-air filters.

EPSS Class / Level

AILevel 1, Type 10 per NFPA 110 (10-second start time)

Gen Specs.pdf - page 5b. 10 seconds.

Gen Specs.pdf - page 5Comply with NFPA 110, Type 10 system requirements.

Gen Specs.pdf - page 4E. EPSS Class: Engine generator shall be classified as a Level 1 according to NFPA 110.

Exhaust Connector End Fittings

AI

Gen Specs.pdf - page 14A. Connect engine exhaust pipe to engine with flexible connector.

Generator Control Alarms

AI

No source-backed value found

Generator Breaker Settings / Trip

AI

Gen Specs.pdf - page 10a. Tripping Characteristics: Adjustable long-time and short-time delay and instantaneous.

Gen Specs.pdf - page 10b. Trip Settings: Selected to coordinate with generator thermal damage curve.

Vibration Isolators

AI

Gen Specs.pdf - page 123. Minimum Additional Travel: 50 percent of required deflection at rated load.

Gen Specs.pdf - page 12A. Restrained Spring Isolators: Freestanding, steel, open-spring isolators.

Gen Specs.pdf - page 126. Minimum Deflection: 1 inch.

Voltage / Frequency Transient Testing

AI

No source-backed value found

Battery Compartment Heater

AI

No source-backed value found

Drawing Generator Rating / One-Line

AIE112 one-line: GENERATOR, 277/480V, 3PH, 4W, 150 KVA. E103 drawing: IBCS-GEN-1, 125 KW DIESEL GENERATOR, 25 hours continuous run time.

Conklin ES - Electrical Drawings.pdf - page 1TO PROVIDE 25 HOURS OF

Conklin ES - Electrical Drawings.pdf - page 2GENERATOR

Conklin ES - Electrical Drawings.pdf - page 1IBCS-GEN-1

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AIOn E112 one-line, breakers connected to generator bus: IBCS-ATS-EM — 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION; IBCS-ATS-X — 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Breakers 100/60 and 250/250 also appear near the generator/switchboard section of the one-line.

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 60A, 35kA

Conklin ES - Electrical Drawings.pdf - page 2250/250

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA

Jacket Water Heater

AI

Gen Specs.pdf - page 6D. Jacket Coolant Heater: Electric-immersion type, factory installed in coolant jacket system.

Exhaust Silencer

AI

Gen Specs.pdf - page 6Minimum sound attenuation of 25 dB at 500 Hz.

Gen Specs.pdf - page 6Sound level measured at a distance of 25 feet from exhaust discharge after installation

Gen Specs.pdf - page 6shall be 78 dBA or less.

Battery and Battery Charger

AI

No source-backed value found

Fuel Tank + Accessories

AI

Gen Specs.pdf - page 83. Leak detection in interstitial space.

Conklin ES - Electrical Drawings.pdf - page 1TO PROVIDE 25 HOURS OF

Gen Specs.pdf - page 85. Containment Provisions: Comply with requirements of authorities having jurisdiction.

Factory Testing

AI

Gen Specs.pdf - page 131. Tests: Comply with IEEE 115 and with NFPA 110, Level 1 Energy Converters.

Field Quality Control / Site Acceptance

AI

No source-backed value found

Load Bank

AI

No source-backed value found

Switchgear / Paralleling

AI

No source-backed value found

Warranty

AI

ATS Specs.pdf - page 21. Warranty Period: 12 months from date of Substantial Completion.

Gen Specs.pdf - page 31. Warranty Period: One year from date of Substantial Completion.

Generator Overload Capacity

AI

Gen Specs.pdf - page 4D. Overload Capacity: 110 percent of service load for 1 hour in 12 consecutive hours.

ATS Requirements13
ATS Quantity

AIquantity: 2 · required: Yes · instances: tag: IBCS-ATS-EM · rating: 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION (E112 one-line); 60 AMP (E103); tag: IBCS-ATS-X · rating: 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION (E112 one-line); 200 AMP (E103)

Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-X

Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-EM

Conklin ES - Electrical Drawings.pdf - page 1IBCS-ATS-X" (200AMP)

ATS Manufacturer / Model

AIASCO Power Technologies; Cummins Power Generation (Basis of Design) OTEC Series

ATS Specs.pdf - page 3ASCO Power Technologies.

ATS Specs.pdf - page 3Cummins Power Generation (Basis of Design) OTEC Series.

ATS Ratings

AI

ATS Specs.pdf - page 21. Short-time withstand capability for 30 cycles.

ATS Specs.pdf - page 3B. Comply with Level 1 equipment according to NFPA 110.

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA

Transition Type

AI

Conklin ES - Electrical Drawings.pdf - page 2OPEN TRANSITION

Poles / Neutral Configuration

AI

ATS Specs.pdf - page 2K. Neutral Terminal: Solid and fully rated.

Conklin ES - Electrical Drawings.pdf - page 23PH, 4W, 4 POLE

ATS Enclosure Type

AI

No source-backed value found

ATS Features / Accessories

AI

No source-backed value found

ATS Transfer Timing

AI

ATS Specs.pdf - page 4b. Time delay adjustable from zero to five minutes, and factory set for five minutes.

ATS Auxiliary Contacts

AI

No source-backed value found

ATS In-Phase Monitor

AI

No source-backed value found

ATS Engine Exerciser

AI

No source-backed value found

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AIInstance 1 — Tag: IBCS-ATS-EM (E103 label: IBCS-ATM-EM); E103 rating: 60 AMP; E112 one-line rating: 277/480V, 60A, 35kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Instance 2 — Tag: IBCS-ATS-X; E103 rating: 200 AMP; E112 one-line rating: 277/480V, 250A, 65kA, 3PH, 4W, 4 POLE, OPEN TRANSITION. Note: E103 shows 200 AMP while E112 one-line shows 250A for IBCS-ATS-X.

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 60A, 35kA

Conklin ES - Electrical Drawings.pdf - page 2277/480V, 250A, 65kA

Conklin ES - Electrical Drawings.pdf - page 2IBCS-ATS-X

ATS Load Sequencing / Shedding

AI

No source-backed value found

Reviewer verdict & notesdraft
Source DocumentsSource Page
PDF
ATS Specs.pdf
PDF
Conklin ES - Electrical Drawings.pdf
PDF