Fenske Road MUD Water Plant

The submission deadline passed before review was completed.

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmWaterEngineers, Inc.Meets
Project LocationCypress, Texas 77433, Harris CountyMeets
Fuel TypeDieselMeets
Size (kW) + QuantityReview
Send to distributorEvidence packet attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Evidence Packet - Fenske Road MUD Water Plant - Due Jul 9, 2026
AttachmentFenske Road MUD Water Plant.pdf
[DISTRIBUTOR NAME], We have a bid opportunity in Harris, TX that fits your coverage area. Details below. Opportunity: Fenske Road MUD Water Plant Contracting Agency: WaterEngineers, Inc. Location: Harris, TX Due Date: Jul 9, 2026 Key Specs: See attached packet for source-backed specifications The evidence packet is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Past due review
Bid value
$0.00
Checks reviewed
0/51 reviewed
Pricing inputs0.48

No defensible Blue Star price is available yet. The submission deadline passed before review was completed.

Found value

$0.00

Configurator/list/base price
$0.00
Active manual adders
$0.00
Reviewed list/base price
$0.00
Distributor net
$0.00
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AIWaterEngineers, Inc.

Specifications - page 1WATERENGINEERS, INC.

Addendum 4 - page 1WATERENGINEERS, INC. TBPE FIRM No. 2066

Contract Docs - Draft Agreement - page 21The Project has been designed by WATERENGINEERS, INC. (TBPE FIRM NO.2066)

Project Location

AICypress, Texas 77433, Harris County

Specifications - page 87Cypress, TX 77433

Contract Docs - Draft Agreement - page 148Counties: Texas Counties of Harris

Engineering Drawings - page 1HARRIS COUNTY, TEXAS

Project Application

AIMunicipal Utility District Water Plant

Contract Docs - Draft Agreement - page 135Fenske Road MUD Water Plant

Addendum 4 - page 2potable water supply system

Specifications - page 1Fenske Road Municipal Utility District Water Plant

Generator Requirements35
Rating Type / Application

AIEmergency/Standby service, Standby rating

Specifications - page 212Standby rating, based on site conditions of altitude 250 ft., ambient temperatures up to 100 degrees F

Specifications - page 212The generator set rating shall be based on emergency/standby service.

Fuel TypePricing input

AIDiesel

Specifications - page 213The engine shall be diesel fueled

Specifications - page 209EMERGENCY/STANDBY POWER SYSTEMS - DIESEL

Size (kW) + QuantityPricing input

AI

Bid Form - Water Well Only - page 2Add Temporary Generator for pump test completion

Contract Docs - Draft Agreement - page 3150 kW diesel generator

Specifications - page 212The generator set shall be rated for the minimum of 250 kW at 0.8 PF.

Voltage + PhasePricing input

AIphase: 3 · voltage: 480/277

Engineering Drawings - page 19480/277 Volt, 4 Wire Service

Alternator Rating / Temp Rise

AIClass H insulation system; actual temperature rise not to exceed 130°C measured by resistance method at full load

Specifications - page 214All insulation system components shall meet NEMA MG1 temperature limits for Class H insulation system. Actual temperature rise measured by resistance method at full load shall not exceed 130 degrees Centigrade.

Voltage Regulator

AIFull wave rectified automatic digital voltage regulation system, three phase RMS sensing, pulse width modulated output, with torque matching characteristic

Specifications - page 217Include a full wave rectified automatic digital voltage regulation system matched and prototype tested by the engine manufacturer

Specifications - page 217The voltage regulation system shall be equipped with three phase RMS sensing and shall control buildup of AC generator voltage to provide a linear rise and limit overshoot.

Generator Space Heater

AI120VAC, minimum 200-watt anti-condensation heater for the alternator

Specifications - page 215Provide a 120VAC, minimum 200-watt anti-condensation heater for the alternator.

Control Panel

AIGenerator set-mounted, vibration-isolated control panel with mode select switch, emergency stop, reset, panel lamp, analog metering, LED alarm/status display, and engine status monitoring

Specifications - page 215The control shall be mounted on the generator set. The control shall be vibration isolated and prototype tested

Control Panel Options / Accessories

AIMode Select Switch (RUN/Manual, OFF, AUTO); EMERGENCY STOP (red mushroom head); RESET Switch; PANEL LAMP Switch; analog metering set (0.5% accuracy, RMS voltage/current/frequency, all three phase voltages simultaneously); LED alarm and status indicating lamps; engine status monitoring (oil pressure, coolant temperature, oil temperature, speed, hours, battery voltage); cycle cranking system (3x15sec crank, 15sec rest); engine governor control with gain/damping/ramping; digital voltage regulation with three-phase RMS sensing and torque matching; AC over/under voltage monitoring; short circuit shutdown protection

Specifications - page 216alarm and status indicating lamps to indicate non automatic generator status

Specifications - page 216analog metering set

Specifications - page 215Mode Select Switch shall initiate the following control modes

Remote Annunciator

AIHard-wired lamp type annunciator panel with audible signal and silencing switch, mounted flush in front panel of ATS; indicating lights grouped for each transfer switch monitored

Specifications - page 205Hard-wired lamp type with audible signal and silencing switch

Specifications - page 206Annunciator Panel Mounting: Mount flush in front panel of ATS.

Enclosure Type + Material

AI

Specifications - page 218The enclosure shall be finish coated with powder baked paint

Specifications - page 218All enclosures are to be constructed from high strength, low alloy steel, aluminum or galvanized steel.

Sound Attenuation

AIMaximum 75 dBA at 7 meters from the generator set in a free field environment at full rated load

Specifications - page 218reduce the sound level of the generator set while operating at full rated load to a maximum of 75 dBA at any location 7 meters from the generator set in a free field environment

Enclosure / Auxiliary-Power Accessories

AIMinimum two doors per side (additional rear door if controller faces rear); stainless steel hinges and hardware (removable doors); lockable latches keyed alike; pitched roof; radiator duct to prevent hot air re-circulation; internal exhaust system or optional external silencer; flame retardant acoustical insulation (mechanically fastened on horizontal planes); exhaust scoop for vertical cooling air direction

Specifications - page 218Doors must be hinged with stainless steel hinges and hardware and be removable

Specifications - page 218A duct between the radiator and air outlet must be provided to prevent re-circulation of hot air

Specifications - page 218Minimum requirements are two doors per side

Circuit Breaker(s)

AIFully rated (100%) 600-volt circuit breaker, mounted in the generator enclosure

Specifications - page 215a fully rated (100%) 600-volt Circuit Breaker, mounted in the generator enclosure

Generator Circuit Breaker

AIFully rated (100%) 600-volt circuit breaker, mounted in the generator enclosure

Specifications - page 215a fully rated (100%) 600-volt Circuit Breaker, mounted in the generator enclosure

Engine Filters

AIFull flow lubrication oil filters with replaceable spin on canister elements and dipstick oil level indicator; replaceable dry element air cleaner with restriction indicator

Specifications - page 213Replaceable dry element air cleaner with restriction indicator

Specifications - page 213Full flow lubrication oil filters with replaceable spin on canister elements and dipstick oil level indicator

EPSS Class / Level

AINFPA 110 Level 1

Specifications - page 203Comply with Level 1 equipment in accordance with to NFPA No.110

Specifications - page 209The generator set shall meet all requirements for Level 1 systems.

Exhaust Connector End Fittings

AI

No source-backed value found

Generator Control Alarms

AILow oil pressure (alarm/shutdown); oil pressure sender failure (alarm); low coolant temperature (alarm); high coolant temperature (alarm/shutdown); engine temperature sender failure (alarm); low coolant level (alarm or shutdown selectable); fail to crank (shutdown); fail to start/over crank (shutdown); overspeed (shutdown); low DC voltage (alarm); high DC voltage (alarm); weak battery (alarm); low fuel day tank (alarm); high AC voltage (shutdown); low AC voltage (shutdown); under frequency (shutdown); emergency stop (shutdown); plus 4 customer specified alarm/shutdown conditions

Specifications - page 216low oil pressure (alarm)

Specifications - page 216emergency stop (shutdown)

Specifications - page 216overspeed (shutdown)

Generator Breaker Settings / Trip

AIOver voltage shutdown: line-to-neutral voltage exceeds 115% for more than 0.5 seconds; AC over voltage shutdown: 110% for more than 10 seconds or 130% with no intentional delay; under voltage shutdown: less than 85% for more than 10 seconds; short circuit shutdown at thermal damage point of alternator; fully rated 600-volt circuit breaker mounted in generator enclosure

Specifications - page 215shut down the generator set if line to neutral voltage on any phase exceeds 115% for more than 0.5 seconds

Specifications - page 217Under voltage shutdown shall occur when the output voltage of the alternator is less than 85% for more than 10 seconds

Specifications - page 217shutdown of the generator set when alternator output voltage exceeds 110% of the operator set voltage level for more than 10 seconds, or with no intentional delay when voltage exceeds 130%

Vibration Isolators

AIControl panel vibration isolated and prototype tested; generator set mounted on heavy-duty steel base to maintain alignment

Specifications - page 215The control shall be vibration isolated and prototype tested

Specifications - page 212The engine generator set shall be mounted on a heavy-duty steel base to maintain alignment between components.

Voltage / Frequency Transient Testing

AIVoltage dip shall not exceed 15% when starting the largest motor last; starting kVA at 15% or less instantaneous voltage dip; manufacturer must submit voltage dip calculations; one-step rated load pickup test per NFPA 110. Note: submittals section references 20% maximum voltage dip limitation.

Specifications - page 210maximum voltage dip limitation of 20%

Specifications - page 212The voltage dip shall not exceed 15% when starting the largest motor last

Specifications - page 219one-step rated load pickup test in accordance with NFPA 110

Battery Compartment Heater

AI

No source-backed value found

Drawing Generator Rating / One-Line

AI

No source-backed value found

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AI

No source-backed value found

Jacket Water Heater

AI

Specifications - page 213Engine mounted, thermostatically controlled, 2500-watt coolant heater. Heater voltage shall be 120V.

Exhaust Silencer

AICritical grade aluminized steel silencer providing 28 to 33 dBA noise reduction

Specifications - page 214Provide a critical grade aluminized steel silencer providing 28 to 33 dBa noise reduction.

Battery and Battery Charger

AIUL listed/CSA certified 10-amp voltage regulated battery charger; float, taper and equalize charge settings; analog DC voltmeter/ammeter; AC and DC fuses; form C contacts (4A, 120VAC, 30VDC) for remote indication of loss of AC power, low/high battery voltage, power ON; batteries: calcium/lead antimony type, 12-volt DC

Specifications - page 214A UL listed/CSA certified 10-amp voltage regulated battery charger shall be provided for each engine generator set.

Specifications - page 214Starting and Control Batteries shall be calcium/lead antimony type, 12-volt DC

Fuel Tank + Accessories

AIUL 142 approved sub-base mounted double wall diesel fuel tank; sized for minimum 48 hours full load operation; with all standard and required vents, direct reading gauge, leak alarm, and low-level alarm

Specifications - page 214A UL 142 approved sub-base mounted double wall diesel fuel tank shall be provided. Tank shall be sized to operate the unit at full load for a minimum of 48 hours. Tank shall be provided with all standard and required vents, direct reading g

Factory Testing

AI

Specifications - page 209Provide factory test, startup by a supplier authorized by the manufacturer

Field Quality Control / Site Acceptance

AIGenerator: cold start test, two-hour full load test, one-step rated load pickup test per NFPA 110; ATS: contact resistance test (max 500 micro-ohms, 50% max adjacent pole difference), ground fault tests, operational tests (minimum 3 times); manufacturer's technician for minimum 2 man-days for ATS and 1/2 man-day for generator instructional services

Specifications - page 207Supplier's or manufacturer's technician for equipment specified herein shall be present at job site for minimum of 2 man-days

Specifications - page 219cold start test, a two-hour full load test and a one-step rated load pickup test in accordance with NFPA 110

Specifications - page 207Contact Resistance Test: Measure resistance of power contacts for ATSs

Load Bank

AI

No source-backed value found

Switchgear / Paralleling

AI

Specifications - page 212for both parallel and non-parallel applications

Warranty

AINot less than 1 year from date of commissioning; comprehensive warranty with no deductibles for travel time, service hours, or repair parts cost

Specifications - page 211The warranty shall be comprehensive. No deductibles shall be allowed for travel time, service hours, repair parts cost, etc.

Specifications - page 211The generator set and associated equipment shall be warranted for a period of not less than 1 year from the date of commissioning against defects in materials and workmanship.

Generator Overload Capacity

AI300% rated current for 10 seconds; 150% of continuous load current for 2 minutes with field set for normal rated load excitation

Specifications - page 214The generator shall be capable of withstanding a three-phase load of 300% rated current for 10 seconds, and sustaining 150% of continuous load current for 2 minutes with field set for normal rated load excitation.

ATS Requirements13
ATS Quantity

AIquantity: 1 · required: Yes · instances: tag: — · rating: —

Specifications - page 200AUTOMATIC TRANSFER SWITCH

Bid Form - Water Plant Only - page 1automatic transfer switch

ATS Manufacturer / Model

AIZenith, ASCO, Onan Corporation, or Kohler (acceptable manufacturers); no specific model designated

Specifications - page 202A. Zenith B. ASCO C. Onan Corporation. D. Kohler

ATS Ratings

AI

Specifications - page 202Number of Poles and Current and Voltage Ratings: As indicated.

Transition Type

AI

No source-backed value found

Poles / Neutral Configuration

AI3-pole with fully rated, solid, unswitched neutral terminal (based on 3-phase 4-wire 480/277V system)

Engineering Drawings - page 19480/277 Volt, 4 Wire Service

Specifications - page 203Where 2- or 3-pole switches are indicated, provide fully rated, solid, unswitched neutral terminal except as indicated.

ATS Enclosure Type

AINEMA 1, general purpose, conforming to UL 508 (except as otherwise indicated); heater for units exposed to outdoor conditions

Specifications - page 203Heater: Within enclosure of units exposed to outdoor temperature and humidity conditions, connect thermostat within enclosure to control heater.

Specifications - page 203Enclosures: General purpose, NEMA 1, conforming to UL 508, except as otherwise indicated.

ATS Features / Accessories

AI

Specifications - page 204Voltage sensing for each phase of normal source

Specifications - page 205Engine-Generator Exerciser: Solid-state programmable time switch

ATS Transfer Timing

AITime-delay override: 1-6 min adjustable; Voltage/Frequency Lockout: voltage pick-up 85-100% (factory 90%), frequency pick-up 90-100% (factory 95%); retransfer time delay: 0-30 min (factory 5 min); signal-before-transfer: 1-30 sec adjustable; engine shut-down: 0-10 min (factory 5 min); motor load time delay: 1-60 secs adjustable per motor

Specifications - page 204Time-delay override of normal source voltage sensing delays transfer and engine start signals. Adjustable 1 to 6 min.

Specifications - page 204Retransfer Time Delay: Adjustable from 0 to 30 min and factory set at 5 min

Specifications - page 204Time delay for individual motor loads is adjustable between 1 and 60 secs

ATS Auxiliary Contacts

AI2 normally open SPDT contacts for each switch position (rating: 10 amps at 240 VAC); engine starting contacts: 1 isolated NC and 1 isolated NO, gold-flashed/gold-plated, rated 10 amps at 32 VDC minimum; engine shut-down contacts: time delay adjustable 0-10 min, factory set 5 min

Specifications - page 2052 normally open SPDT contacts for each switch position

Specifications - page 205Engine Starting Contacts: One isolated normally closed and 1 isolated normally open. Contacts are gold-flashed or gold-plated and rated 10 amps at 32 vdc minimum.

ATS In-Phase Monitor

AI

No source-backed value found

ATS Engine Exerciser

AISolid-state programmable time switch; starts engine-generator and transfers load for preset time, then retransfers and shuts down after cool-down; intervals adjustable 7-30 days (factory 7 days); running periods 10-60 min (factory 30 min); exerciser transfer selector switch (with/without load transfer); pushbutton programming with digital display; integral battery operation when normal control power unavailable

Specifications - page 205Solid-state programmable time switch starts engine-generator set and transfers load to it from normal source for preset time

Specifications - page 205Initiate exercise cycle at preset intervals adjustable from 7 to 30 days. Running periods are adjustable from 10 to 60.

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AI

No source-backed value found

ATS Load Sequencing / Shedding

AIInternal motor control undervoltage and timing relays (where indicated); de-energize motors prior to transfer and re-energize selectively at adjustable time intervals after transfer; time delay for individual motor loads adjustable 1-60 secs; control connection to motor starters through wiring external to ATS

Specifications - page 204ATS includes factory-installed and factory-wired internal motor control undervoltage and timing relays. Relays control designated starters to de-energize motors prior to transfer and re-energize them selectively at adjustable time intervals

Reviewer verdict & notesdraft
Source DocumentsSource Page
PDF
Addendum%20No.%2003.pdf
PDF
01-Addendum%202%20-%20Fenske.pdf
PDF
01-Addendum%201%20-%20Fenske.pdf
PDF
02-SPECS%20-%20Fenske%20Road%20MUD%20Bidding.pdf
PDF
04-%20Bid%20Form%20-%20Fenske%20Well%20No.%201%20(Phase%20I).pdf
PDF
03-Drawings%20-%20Fenske%20Road%20MUD%20Bidding.pdf
PDF
01-Contract%20Docs%20-%20Fenske%20Road%20MUD%20Bidding.pdf
PDF
Addendum%20No.%2004.pdf
PDF
25-734E%20-Revised%20Geotech%20Report%20-%20Fenshire%20Development%20Company.pdf
PDF
04-Bid%20Form%20-%20Fenske%20Water%20Plant%20(Phase%20I).pdf