Generator Spec.pdf - page 1STANTEC PROJECT 218012164
E-510.pdf - page 1Stantec
Resolve the submission deadline before treating this opportunity as active.
| Field Check | Found Value | Status |
|---|---|---|
| Engineering Firm | Stantec | Meets |
| Project Location | — | Review |
| Fuel Type | Natural gas | Meets |
| Size (kW) + Quantity | Line 1: 1 × 1000 kW · natural gas · 480 V ac, 3 PH · permanent | Meets |
A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. Resolve the submission deadline before treating this opportunity as active.
$794,420.00
AIStantec
Generator Spec.pdf - page 1STANTEC PROJECT 218012164
E-510.pdf - page 1Stantec
AI—
No source-backed value found
AIFulfillment Center
Generator Spec.pdf - page 1EVY1 – FULFILLMENT CENTER
AIStandby (power rating); Emergency / Level 1 EPSS (application)
E-510.pdf - page 1EMERGENCY GENERATOR
Generator Spec.pdf - page 4Comply with NFPA 110 requirements for Level 1 EPSS.
Generator Spec.pdf - page 5Power Rating: Standby.
AINatural gas
Generator Spec.pdf - page 8Natural Gas, Vapor-Withdrawal System:
Single Line.pdf - page 1DESIGN IS BASED ON NATURAL GAS FIRED EMERGENCY
Generator Spec.pdf - page 6Fuel: Natural gas.
AILine 1: 1 × 1000 kW · natural gas · 480 V ac, 3 PH · permanent
Generator Spec.pdf - page 51250 kVA/1000 kW
Generator Spec.pdf - page 5GAS-ENGINE-DRIVEN GENERATOR SETS
Generator Spec.pdf - page 5480 V ac
AIphase: 3 · voltage: 480V
Generator Spec.pdf - page 5Phase: Three-phase, four wire, wye.
E-510.pdf - page 1480/271V, 3P, 4W
Generator Spec.pdf - page 5Voltage: 480 V ac.
AIClass H insulation; 12% maximum subtransient reactance; 125°C temperature rise per one-line
Generator Spec.pdf - page 12Electrical Insulation: Class H.
Generator Spec.pdf - page 12Subtransient Reactance: 12 percent, maximum.
E-510.pdf - page 11000KW (125C) ALTERNATOR
AI—
Generator Spec.pdf - page 12Maintain voltage within 15 percent on one step, full load.
Generator Spec.pdf - page 12Provide anti-hunt provision to stabilize voltage.
Generator Spec.pdf - page 6Provide permanent magnet excitation for power source to voltage regulator.
AIStrip Heater: Thermostatically controlled unit arranged to maintain stator windings above dew point.
Generator Spec.pdf - page 12Strip Heater: Thermostatically controlled unit arranged to maintain stator windings above dew point.
AI—
No source-backed value found
AIInstruments: Engine lubricating-oil pressure gage, engine-coolant temperature gage, DC voltmeter (alternator battery charging), running-time meter, AC voltmeter (each phase), AC ammeter (each phase), AC frequency meter, generator-voltage adjusting rheostat. Engine generator metering: voltage, current, Hz, kW, kVA, power factor. Modbus TCP communication interface to Division 23 BAS. Remote emergency-stop switch (flush, wall mounted, labeled, protected from accidental operation). Minimum run time control set for 15 minutes.
Generator Spec.pdf - page 9Generator-voltage adjusting rheostat.
Generator Spec.pdf - page 9AC voltmeter, for each phase.
Generator Spec.pdf - page 11Provide Modbus TCP communication interface to communicate with Division 23 Building Automation System.
AI—
No source-backed value found
AIVandal-resistant, sound-attenuating, weatherproof steel housing, galvanized-steel-clad, integral structural-steel-framed, Level 1 enclosure (NFPA 110), not walk-in style, NEMA 3R, service-entrance rated, wind resistant up to 100 mph (ASCE/SEI 7).
Generator Spec.pdf - page 13Level 1 enclosure
Generator Spec.pdf - page 13Enclosure is not considered "walk-in" style.
E-510.pdf - page 1(SERVICE-ENTRANCE RATED)
AI—
Generator Spec.pdf - page 7Est sound level at 25ft = 79dBA - 80dBA.
Generator Spec.pdf - page 7Minimum sound attenuation of 25 dB at 500 Hz.
AIHinged doors with padlocking provisions; thermostatically controlled space heater (prevent condensation); weather-resistant LED lighting (30 fc average maintained); GFCI convenience outlets (factory wired); automatic dampers at engine cooling-air inlet and discharge; storm-proof drainable louvers; interior lights with switch (vapor-proof, factory-wired); thermal insulation; AC lighting system with external connection point.
Generator Spec.pdf - page 13Louvers: Fixed-engine, cooling-air inlet and discharge. Storm-proof and drainable louvers
Generator Spec.pdf - page 13Automatic Dampers: At engine cooling-air inlet and discharge.
Generator Spec.pdf - page 13Lighting: Provide weather-resistant LED lighting with 30 fc average maintained.
AI—
Generator Spec.pdf - page 11Insulated-case circuit breaker, electronic-trip type; 100 percent rated; complying with UL 489:
E-510.pdf - page 1600/3P, NON-FUSED
AI—
Generator Spec.pdf - page 11Insulated-case circuit breaker, electronic-trip type; 100 percent rated; complying with UL 489:
Generator Spec.pdf - page 12Mounting: Adjacent to, or integrated with control and monitoring panel.
AIAir-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element and 'blocked filter' indicator. Lubrication System Filter: Rated to remove 90% of particles 5 micrometers and smaller while passing full flow. Spare parts: (qty 6) Oil Filter p/n 32124; (qty 2) Air Filter p/n 27007; (qty 2) Gasket Air Filter p/n 32123.
Generator Spec.pdf - page 7Air-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element
Generator Spec.pdf - page 3(qty 6) Oil Filter - p/n 32124.
Generator Spec.pdf - page 6Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller
AINFPA 110 Level 1 EPSS, Class 48, Type 10 system
Generator Spec.pdf - page 5EPSS Class: Engine generator shall be classified as Class 48 according to NFPA 110.
Generator Spec.pdf - page 6Comply with NFPA 110, Type 10 system requirements.
Generator Spec.pdf - page 4Comply with NFPA 110 requirements for Level 1 EPSS.
AIFlexible connector required between engine exhaust pipe and engine (spec 3.3.C). End fittings for exhaust connector are not specified.
Generator Spec.pdf - page 15Connect engine exhaust pipe to engine with flexible connector.
AICranking control equipment; Run-Off-Auto switch; Control switch not in auto alarm; Overcrank alarm/shutdown; Low water temperature alarm; High engine temperature prealarm/alarm/shutdown; Overspeed alarm/shutdown; Coolant low-level alarm/shutdown; Coolant high-temperature prealarm/alarm/shutdown; Coolant low-temperature alarm; EPS supplying load indicator; Battery high-voltage alarm; Low cranking voltage alarm; Battery-charger malfunction alarm; Battery low-voltage alarm; Lamp test; Contacts for local and remote common alarm; Hours of operation; Engine generator metering (V, A, Hz, kW, kVA, PF); Generator overcurrent protective device not closed alarm.
Generator Spec.pdf - page 9High engine temperature shutdown device.
Generator Spec.pdf - page 10Generator overcurrent protective device not closed alarm.
Generator Spec.pdf - page 9Overspeed shutdown device.
AIAdjustable long-time and short-time delay and instantaneous. Trip settings selected to coordinate with generator thermal damage curve. Shunt trip connected to trip breaker when engine generator is shut down by other protective devices. 100 percent rated.
Generator Spec.pdf - page 11Trip Settings: Selected to coordinate with generator thermal damage curve.
Generator Spec.pdf - page 12Shunt Trip: Connected to trip breaker when engine generator is shut down by other protective devices.
Generator Spec.pdf - page 11Tripping Characteristics: Adjustable long-time and short-time delay and instantaneous.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
E-510.pdf - page 1(SERVICE-ENTRANCE RATED)
E-510.pdf - page 1NEMA '3R' ENCLOSURE
E-510.pdf - page 1480/271V, 3P, 4W
AI—
E-510.pdf - page 1600/3P, NON-FUSED
AI—
No source-backed value found
AI—
Generator Spec.pdf - page 13Muffler Location: Within enclosure.
Generator Spec.pdf - page 7Minimum sound attenuation of 25 dB at 500 Hz.
Generator Spec.pdf - page 7Critical type, sized as recommended by engine manufacturer
AI—
Generator Spec.pdf - page 8Equalizing-charging rate of 10 A
Generator Spec.pdf - page 8NEMA 250, Type 1, wall-mounted cabinet.
Generator Spec.pdf - page 7Battery: Lead acid, with capacity within ambient temperature range specified
AI—
Generator Spec.pdf - page 8Fuel-Shutoff Solenoid Valves: NRTL-listed, normally closed, safety shutoff valves; one for each fuel source.
Generator Spec.pdf - page 8Flexible Fuel Connectors: Minimum one for each fuel connection.
Generator Spec.pdf - page 8Fuel Filters: One for each fuel type.
AI—
Generator Spec.pdf - page 14Tests: Comply with IEEE 115 and with NFPA 110, Level 1 Energy Converters.
Generator Spec.pdf - page 14Full load run.
Generator Spec.pdf - page 14Single-step load pickup.
AI—
Generator Spec.pdf - page 16Perform insulation-resistance tests in accordance with IEEE 43.
Generator Spec.pdf - page 17Infrared Scanning: After Substantial Completion, but not more than 60 days after final acceptance
Generator Spec.pdf - page 16NFPA 110 Acceptance Tests: Perform tests required by NFPA 110
AILoad bank included in Section 263213.16 scope (Section Includes, item 6). No further specification details provided.
Generator Spec.pdf - page 1Load bank.
AI—
No source-backed value found
AIManufacturer's Warranty: 5 years from date of Substantial Completion. Manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship. Initial Maintenance Service: 12 months full maintenance beginning at Substantial Completion.
Generator Spec.pdf - page 3Warranty Period: 5 years from date of Substantial Completion.
AI—
Generator Spec.pdf - page 12heat during operation at 110 percent of rated capacity.
AIquantity: 10 · required: Yes · instances: tag: ATS-SMDFA · rating: 400A, 4P, W/BYPASS, SHUNT TRIP; tag: ATS-SMDFD · rating: 400A, 4P, W/BYPASS, SHUNT TRIP; tag: ATS-SA · rating: 150A (1414c4a8 p1) / 600A, 4P, W/BYPASS, SHUNT TRIP (3830073f p1) — CONFLICT; tag: ATS-SB · rating: 150A (1414c4a8 p1 feeder schedule); tag: ATS-SC · rating: 150A (1414c4a8 p1 feeder schedule); tag: ATS-SD · rating: 150A (1414c4a8 p1) / 260A, 4P (3830073f p1) — CONFLICT; tag: ATS-EA · rating: 260A, 4P, W/BYPASS (1414c4a8 p1) / 400A, 4P, W/BYPASS, SHUNT (3830073f p1) — CONFLICT; tag: ATS-EB · rating: 260A, 4P, W/BYPASS; tag: ATS-EC · rating: 260A, 4P, W/BYPASS; tag: ATS-ED · rating: 260A, 4P, W/BYPASS
E-510.pdf - page 1ATS-SC
E-510.pdf - page 1ATS-EB
E-510.pdf - page 1ATS-SMDFD-1
AI—
No source-backed value found
AI—
E-510.pdf - page 1260A, 4-POLE
AI—
E-510.pdf - page 1260A, 4-POLE
AI—
Single Line.pdf - page 1400A/4P
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found