Replace Radar Generator, B2021

Compliance matrix4 checks shown
Field CheckFound ValueStatus
Engineering FirmReview
Project LocationColumbus AFB, MississippiMeets
Fuel TypeDieselMeets
Size (kW) + QuantityLine 1: 1 × 102 kW · Diesel · 277/480, 3 PH · permanent; Line 2: 2 × 102 kW · Diesel · 277/480, 3 PH · temporaryMeets
Send to distributorFormal proposal attached
Distributor assignment has not been synced for this bid yet.
SubjectBlue Star Formal Proposal - Replace Radar Generator, B2021 - Due Jul 20, 2026
AttachmentReplace Radar Generator, B2021.pdf
[DISTRIBUTOR NAME], We have a bid opportunity in Columbus, MS that fits your coverage area. Details below. Opportunity: Replace Radar Generator, B2021 Contracting Agency: Unknown federal buyer Location: Columbus, MS Due Date: Jul 20, 2026 Key Specs: 1 × PD125-01 The formal proposal is attached as a PDF with the current configuration direction, compliance matrix, and supporting documentation. Let us know if you have questions or need any changes before submitting. Best, [YOUR NAME] Blue Star Power Systems
Copy keeps both HTML and plain text.
Employee review
Review workspace
Loading packet preview...
Review notes
Distributor assignment has not been synced for this bid yet.
Review status
Business bucket
Priced
Bid value
$30,216.00
Checks reviewed
0/51 reviewed
Reviewed pricing0.48
Found value

$62,950.00

Configurator/list/base price
$62,950.00
Active manual adders
$0.00
Reviewed list/base price
$62,950.00
Distributor net
$30,216.00
1 × PD125-01
102 kW · Diesel · $62,950.00
2 × temporary
102 kW · Diesel · Not charged
Distributor multiplierControls reviewed net pricing
New manual adderSaved as active reviewer pricing provenance
Active on save
No manual pricing adders have been saved.
Packet regenerationNo generated packet is recorded.
Field checks
51
Add Field Check itemField checks do not change price. Add price impact under Reviewed pricing.
Project Overview3
Engineering Firm

AI

No source-backed value found

Project Location

AIColumbus AFB, Mississippi

Solicitation - FA302226R0006.pdf - page 1Project Location: Columbus AFB

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 1COLUMBUS AFB, MISSISSIPPI

Project Application

AI

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6B2021 is the Radar site for Columbus AFB.

Generator Requirements35
Rating Type / Application

AIStandby

extract Kohler Raytheon EG Electrical.pdf - page 4Nameplate Rating Standby

extract Kohler Raytheon EG Electrical.pdf - page 7Standby130C Ratings

Fuel TypePricing input

AIDiesel

extract Kohler Raytheon EG Electrical.pdf - page 3Fuel Type - Diesel

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6new diesel Cummins generator

Size (kW) + QuantityPricing input

AILine 1: 1 × 102 kW · Diesel · 277/480, 3 PH · permanent; Line 2: 2 × 102 kW · Diesel · 277/480, 3 PH · temporary

extract Kohler Raytheon EG Electrical.pdf - page 3Output- 102.0kW, 128 KVA, 277/480 Volt, 153 Amps,60 Hz , Three Phase

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6The mobile generator supporting this facility must consist of two generators wired in parallel, with each generator individually being capable of supporting the facility.

Voltage + PhasePricing input

AIphase: 3 · voltage: 277/480

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6277/480V 128 kVA Kohler generator

extract Kohler Raytheon EG Electrical.pdf - page 3277/480 Volt, 153 Amps,60 Hz , Three Phase

Alternator Rating / Temp Rise

AI130°C, Standby

extract Kohler Raytheon EG Electrical.pdf - page 8Insulation: Temperature Rise 130°C, Standby

Voltage Regulator

AI

extract Kohler Raytheon EG Electrical.pdf - page 8Voltage regulator Solid State, Volts/Hz

Generator Space Heater

AIGenerator Heater

extract Kohler Raytheon EG Electrical.pdf - page 4Electrical Accy.,Installed Generator Heater

Control Panel

AI

extract Kohler Raytheon EG Electrical.pdf - page 4Controller APM603

Control Panel Options / Accessories

AI7-inch color TFT touchscreen; 15 Relay I/O Board; Run Relay; Failure Relay w/Harness, 1 Fault; Modbus/SNMP/BACnet/Ethernet/RS-485/USB communications; alternator protection; cyclic cranking; ECU diagnostics; remote reset; remote monitoring panel (RSA) compatible; load management up to 16 prioritized load steps; overcurrent protective device; maintenance mode for arc flash reduction

extract Kohler Raytheon EG Electrical.pdf - page 415 Relay I/O Board

extract Kohler Raytheon EG Electrical.pdf - page 117-inch color TFT touchscreen

extract Kohler Raytheon EG Electrical.pdf - page 13Supports up to 16 prioritized load steps per system

Remote Annunciator

AIExisting annunciator panel; new generator shall be wired into existing system by contractor

B2021 RFI_Answers.docx - page 1Existing annunciator panel PLC information attached, the new generator shall be wired into existing system by contractor.

Enclosure Type + Material

AIOpen (existing; generator located inside generator shed)

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6reutilizing existing penetrations in the generator shed

extract Kohler Raytheon EG Electrical.pdf - page 3Enclosure - Open

Sound Attenuation

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Enclosure - Open

Enclosure / Auxiliary-Power Accessories

AIRadiator Duct Flange; Skid 34"; Flexible Fuel Lines; Air Cleaner Restriction Ind.; Coolant in Genset

extract Kohler Raytheon EG Electrical.pdf - page 4Skid and Mounting Skid, 34"

extract Kohler Raytheon EG Electrical.pdf - page 4Cooling System Acc.,Installed Radiator Duct Flange

Circuit Breaker(s)

AI

extract Kohler Raytheon EG Electrical.pdf - page 4Amps, LCB 2 LOAD BANK 150

extract Kohler Raytheon EG Electrical.pdf - page 4Rating, LCB 1 100% Rated

Generator Circuit Breaker

AILCB 1: 100% Rated, 200A, Thermal Magnetic, 18kA at 480V, Shunt Trip

extract Kohler Raytheon EG Electrical.pdf - page 4Rating, LCB 1 100% Rated

extract Kohler Raytheon EG Electrical.pdf - page 4Trip Type, LCB 1 Thermal Magnetic

extract Kohler Raytheon EG Electrical.pdf - page 4Amps, LCB 1 200

Engine Filters

AIFuel Filter Secondary: 2 Microns @ 98% Efficiency; Fuel Filter Primary: 30 Microns; Fuel Filter Water Separator: Yes; Oil filter: 1, Cartridge; Air cleaner: Dry

extract Kohler Raytheon EG Electrical.pdf - page 9Fuel Filter Secondary 2 Microns@ 98% Efficiency

extract Kohler Raytheon EG Electrical.pdf - page 8Air cleaner type, all models Dry

extract Kohler Raytheon EG Electrical.pdf - page 9Fuel Filter Primary 30 Microns

EPSS Class / Level

AINFPA 110, Level 1

extract Kohler Raytheon EG Electrical.pdf - page 13NFPA 110, Level 1

extract Kohler Raytheon EG Electrical.pdf - page 7The 60 Hz generator set meets NFPA 110, Level 1

Exhaust Connector End Fittings

AI4" NPT

extract Kohler Raytheon EG Electrical.pdf - page 5Exhaust Conn,4"NPT Battery Charger

extract Kohler Raytheon EG Electrical.pdf - page 27Flex Exhaust 4NPT

Generator Control Alarms

AI

extract Kohler Raytheon EG Electrical.pdf - page 14Over Crank Shutdown [ D

Generator Breaker Settings / Trip

AI

extract Kohler Raytheon EG Electrical.pdf - page 4Amps, LCB 2 LOAD BANK 150

extract Kohler Raytheon EG Electrical.pdf - page 4Rating, LCB 1 100% Rated

Vibration Isolators

AI

No source-backed value found

Voltage / Frequency Transient Testing

AI

extract Kohler Raytheon EG Electrical.pdf - page 8One-Step Load Acceptance 100% of rating

Battery Compartment Heater

AI

No source-backed value found

Drawing Generator Rating / One-Line

AI

No source-backed value found

One-Line Generator Breaker Ratings (spatially connected main and auxiliary breakers)

AILCB 1 (main): 200A, Thermal Magnetic, 18kA@480V, Shunt Trip; LCB 2 (load bank): 150A, Thermal Magnetic, 18kA@480V, Shunt Trip

extract Kohler Raytheon EG Electrical.pdf - page 4Amps, LCB 2 LOAD BANK 150

extract Kohler Raytheon EG Electrical.pdf - page 4Interrupt Rating LCB 1 18kA at 480V

extract Kohler Raytheon EG Electrical.pdf - page 4Amps, LCB 1 200

Jacket Water Heater

AI1500W, 120V (Starting Aid); preheat system required

extract Kohler Raytheon EG Electrical.pdf - page 4Starting Aids, Installed 1500W,120V

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 6this generator has unique requirements, such as a preheat system

Exhaust Silencer

AICritical, 4" NPT, SIEO (25-35 dB(A) noise reduction)

extract Kohler Raytheon EG Electrical.pdf - page 5Silencer,Critical,4"NPT,SIEO Flexible

extract Kohler Raytheon EG Electrical.pdf - page 26Critical Silencer SIEO - 4 NPT

Battery and Battery Charger

AI10A, 12/24VDC automatic multi-stage charger; Battery: 12V, 640 CCA, Wet

extract Kohler Raytheon EG Electrical.pdf - page 4Battery Charger, 10A

extract Kohler Raytheon EG Electrical.pdf - page 2412/24 Volt, 10 Amp

extract Kohler Raytheon EG Electrical.pdf - page 4Battery, 1/12V, Wet

Fuel Tank + Accessories

AI

extract Kohler Raytheon EG Electrical.pdf - page 325 Gallon Day Tank

extract Kohler Raytheon EG Electrical.pdf - page 4Fuel Lines, Installed Flexible Fuel Lines

Factory Testing

AI

extract Kohler Raytheon EG Electrical.pdf - page 5Power Factor Test,0.8,3Ph Only

extract Kohler Raytheon EG Electrical.pdf - page 4UL2200 Listing

Field Quality Control / Site Acceptance

AIStart-up service with NFPA 110 Load Test

extract Kohler Raytheon EG Electrical.pdf - page 3Start-up Service with NFPA 110 Load Test

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 7The Contractor shall be responsible for providing start-up service with NFPA 110 Load Test.

Load Bank

AI

No source-backed value found

Switchgear / Paralleling

AI

extract Kohler Raytheon EG Electrical.pdf - page 13Supports paralleling up to 8 generators

Warranty

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Warranty - 2 Year Basic

Generator Overload Capacity

AINo overload capability for Standby rating

extract Kohler Raytheon EG Electrical.pdf - page 7There is no overload capability for this rating.

ATS Requirements13
ATS Quantity

AIquantity: 1 · required: Yes · instances: tag: ATS 1500 · rating: 260 Amps

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 7Demolish existing ATS 1500 Transfer Switch System. Furnish and install new transfer switch system that matches capabilities of the existing ATS system.

extract Kohler Raytheon EG Electrical.pdf - page 3Type - Bypass\Isolation, Open Transition, 480 Volts/60Hz, 260 Amps

ATS Manufacturer / Model

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Kohler KBS-DMWA-0260S Transfer Switch

ATS Ratings

AI260 Amps, 480V/60Hz

extract Kohler Raytheon EG Electrical.pdf - page 3480 Volts/60Hz, 260 Amps

extract Kohler Raytheon EG Electrical.pdf - page 5Amps 260 Amps

Transition Type

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Type - Bypass\Isolation, Open Transition

Poles / Neutral Configuration

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Poles - 4-Pole, 4-Wire, Overlapping Neutral

ATS Enclosure Type

AI

extract Kohler Raytheon EG Electrical.pdf - page 3Enclosure - NEMA 1 Enclosure

ATS Features / Accessories

AIBypass isolation; drawout contactor; Decision-Maker MPAC 1500 controller; Input/Output Module; Current Sensing; programmable voltage/frequency sensing; programmable time delays; generator exerciser; in-phase monitor; load bank control; load control (9 time delays); Modbus/Ethernet/RS-485/USB communications; 3-source system capability; supervised transfer control

extract Kohler Raytheon EG Electrical.pdf - page 39In-phase monitor (3-phase only)

SOW EEPZ248376 Replace Radar Generator B2021.pdf - page 7The existing ATS uses the Decision-Maker MPAC 1500, Automatic controller.

extract Kohler Raytheon EG Electrical.pdf - page 5Current Sensing

ATS Transfer Timing

AI

extract Kohler Raytheon EG Electrical.pdf - page 41Engine start, Source S2 3 sec.

ATS Auxiliary Contacts

AI8 contacts indicating Normal, 8 contacts indicating Emergency (rated 10 Amps @ 32 VDC/250 VAC)

extract Kohler Raytheon EG Electrical.pdf - page 33(rated 10 Amps @ 32 VDC/250 VAC)

extract Kohler Raytheon EG Electrical.pdf - page 33260 8, 8

ATS In-Phase Monitor

AI

extract Kohler Raytheon EG Electrical.pdf - page 39In-phase monitor (3-phase only)

ATS Engine Exerciser

AI

extract Kohler Raytheon EG Electrical.pdf - page 40Exerciser: calendar mode, loaded/unloaded up to 21 events

ATS Configuration Schedule (every distinct tagged instance kept separate by page/location, with rating, poles, and service rating)

AIExisting: Mechanism Bypass Type B; Transition Standard; Logic 1500 (Decision-Maker MPAC 1500); Voltage 480V/60Hz; Poles 4 Pole/4 Wire Overlapping Neutral; Enclosure NEMA 1; Amps 260; Connection Standard. New ATS to match capabilities, 4 Pole/4 Wire overlapping neutral.

extract Kohler Raytheon EG Electrical.pdf - page 5Poles & Wires 4 Pole/4Wire, Overlapping Neut

extract Kohler Raytheon EG Electrical.pdf - page 5Logic 1500

extract Kohler Raytheon EG Electrical.pdf - page 5Enclosure Nema 1

ATS Load Sequencing / Shedding

AI

extract Kohler Raytheon EG Electrical.pdf - page 39Load bank control for exercise or test

extract Kohler Raytheon EG Electrical.pdf - page 13Supports up to 16 prioritized load steps per system

Reviewer verdict & notesdraft
Source DocumentsSource Page
DOC
Form+66+EEPZ249376+Replace+Radar+Generator.xlsx
DOC
MFR+CUI+Contractor+Training+Acknowledgment+July+2024.pdf
DOC
Appendix+A+-+Cost+Breakdown.xlsx
DOC
Solicitation+Amendment+FA302226R00060002+SF+30.pdf
DOC
extract+Kohler+Raytheon+EG+Electrical.pdf
DOC
Solicitation+-+FA302226R0006.pdf
DOC
SOW+EEPZ248376+Replace+Radar+Generator+B2021.pdf
DOC
Solicitation+Amendment+FA302226R00060001+SF+30.pdf
DOC
sam-gov-notice-description.html
DOC
Contractors+CUI+Training+Slides.pptx
DOC
B2021+RFI_Answers.docx
DOC
EAL+Form.pdf
DOC
Wage+Determination.pdf
DOC
B2021+site+visit+sign+in+sheet.pdf
DOC
CAFB+Standards.pdf