AI—
No source-backed value found
Resolve the submission deadline before treating this opportunity as active.
| Field Check | Found Value | Status |
|---|---|---|
| Engineering Firm | — | Review |
| Project Location | — | Review |
| Fuel Type | Diesel (ASTM D975, Grade 2-D S15) | Meets |
| Size (kW) + Quantity | Line 1: 1 × 250 kVA · Diesel · 480, 3 PH · permanent | Meets |
A Blue Star configuration exists, but it is not an approved opportunity price until review is resolved. Resolve the submission deadline before treating this opportunity as active.
$83,830.00
AI—
No source-backed value found
AI—
No source-backed value found
AIPackaged engine generators used to supply non-emergency power
Gen Specs.pdf - page 1packaged engine generators used to supply non-emergency power
AIStandby
Gen Specs.pdf - page 3Power Rating: Standby.
AIDiesel (ASTM D975, Grade 2-D S15)
Gen Specs.pdf - page 4Fuel: ASTM D975, diesel fuel oil, Grade 2-D S15.
Gen Specs.pdf - page 1Diesel engine.
AILine 1: 1 × 250 kVA · Diesel · 480, 3 PH · permanent
Gen Specs.pdf - page 2Blue Star Power Systems
Gen Specs.pdf - page 3Voltage: 480-V ac.
Gen Specs.pdf - page 3Phase: Three-phase, four wire, wye.
AIphase: 3 · voltage: 480
Gen Specs.pdf - page 3Voltage: 480-V ac.
Gen Specs.pdf - page 3Phase: Three-phase, four wire, wye.
AIClass H insulation; Subtransient Reactance: 12 percent, maximum
Gen Specs.pdf - page 9Subtransient Reactance: 12 percent, maximum.
Gen Specs.pdf - page 8Electrical Insulation: Class H.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AIDripproof
Gen Specs.pdf - page 9Enclosure: Dripproof.
AI—
Gen Specs.pdf - page 4Minimum sound attenuation of 25 dB at 500 Hz.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AILube oil filter and strainer (90% of particles 5 micrometers and smaller); fuel filtering (1 micron); air-intake filter with replaceable dry-filter element and blocked filter indicator
Gen Specs.pdf - page 5Fuel Filtering: Remove water and contaminants larger than 1 micron.
Gen Specs.pdf - page 5Air-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element
Gen Specs.pdf - page 4Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller
AILevel 2 EPSS; Class 24; Type 10 per NFPA 110
Gen Specs.pdf - page 3EPSS Class: Engine generator shall be classified as a Class 24 according to NFPA 110.
Gen Specs.pdf - page 2Comply with NFPA 110 requirements for Level 2 EPSS.
Gen Specs.pdf - page 4Comply with NFPA 110, Type 10 system requirements.
AI—
No source-backed value found
AI—
No source-backed value found
AITripping Characteristic: Designed specifically for generator protection; Trip Rating: Matched to generator output rating
Gen Specs.pdf - page 8Tripping Characteristic: Designed specifically for generator protection.
AIElastomeric isolator pads (oil- and water-resistant elastomer or natural rubber with galvanized-steel baseplates); restrained spring isolators with seismic restraint (steel, freestanding, open-spring)
Gen Specs.pdf - page 9Elastomeric Isolator Pads: Oil- and water-resistant elastomer or natural rubber
Gen Specs.pdf - page 9Restrained Spring Isolators: Freestanding, steel, open-spring isolators with seismic restraint.
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AICritical type, sized as recommended by engine manufacturer; minimum 25 dB attenuation at 500 Hz; 78 dBA or less at 25 feet
Gen Specs.pdf - page 4Muffler/Silencer: Critical type, sized as recommended by engine manufacturer
Gen Specs.pdf - page 4Minimum sound attenuation of 25 dB at 500 Hz.
AI—
Gen Specs.pdf - page 5Enclosure and Mounting: NEMA 250, Type 1, wall-mounted cabinet.
AI—
Gen Specs.pdf - page 324HR Capacity + 33% extra = 500 gal
Gen Specs.pdf - page 6Leak detection in interstitial space.
Gen Specs.pdf - page 6Tank level indicator.
AIFactory-assembled and -tested; prototype testing per IEEE 115 using same engine model with identical or equivalent components
Gen Specs.pdf - page 10Prototype Testing: Factory test engine generator using same engine model
Gen Specs.pdf - page 2Factory-assembled and -tested, water-cooled engine, with brushless generator and accessories.
AI—
Gen Specs.pdf - page 11Perform insulation-resistance tests according to IEEE 43.
Gen Specs.pdf - page 11Test protective relay devices.
AI—
No source-backed value found
AI—
No source-backed value found
AIOne year from date of Substantial Completion
Gen Specs.pdf - page 2Warranty Period: one year from date of Substantial Completion.
AI110 percent of service load for 1 hour in 12 consecutive hours
Gen Specs.pdf - page 3Overload Capacity: 110 percent of service load for 1 hour in 12 consecutive hours.
AI—
No source-backed value found
AIASCO Series 300 (3ATS)
ATS Specs.pdf - page 1Automatic transfer switches shall be ASCO Series 300 (3ATS).
AI—
No source-backed value found
AIOpen transition or delayed transition
ATS Specs.pdf - page 3Transfer operating mode configuration, (open transition, or delayed transition)
AI—
No source-backed value found
AI—
No source-backed value found
AI—
ATS Specs.pdf - page 6Provide the ability to select “commit/no commit to transfer”
ATS Specs.pdf - page 6A variable window in phase monitor shall be provided in the controller
ATS Specs.pdf - page 3A 128*64 graphical LCD display and keypad shall be an integral part of the controller
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found
AI—
No source-backed value found